Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from centre point (m) |
||||
-2 |
1 |
1.39 |
50 |
1.39 |
-1 |
1 |
1.41 |
51 |
1.43 |
0 |
1 |
1.52 |
51 |
1.55 |
1 |
1 |
1.52 |
50 |
1.52 |
2 |
1 |
1.47 |
51 |
1.50 |
Starting Point |
Measurement height (m) |
Electric field level (V/m) |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from centre point (m) |
||||
-2 |
1 |
258.35 |
51 |
5.27 |
-1 |
1 |
259.50 |
50 |
5.19 |
0 |
1 |
252.80 |
50 |
5.06 |
1 |
1 |
256.19 |
51 |
5.23 |
2 |
1 |
252.45 |
51 |
5.15 |
Magnetic and electric field
level measurements overhead power lines, longitudinal profile.
Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from centre point (m) |
||||
-2 |
1 |
1.41 |
50 |
1.41 |
-1 |
1 |
1.44 |
51 |
1.47 |
0 |
1 |
1.52 |
51 |
1.55 |
1 |
1 |
1.36 |
50 |
1.36 |
2 |
1 |
1.30 |
51 |
1.33 |
Starting Point |
Measurement height (m) |
Electric field level (V/m) |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from centre point (m) |
||||
-2 |
1 |
260.59 |
50 |
5.21 |
-1 |
1 |
254.38 |
51 |
5.19 |
0 |
1 |
252.80 |
50 |
5.06 |
1 |
1 |
257.09 |
50 |
5.14 |
2 |
1 |
251.20 |
51 |
5.12 |
Magnetic and electric field level measurements overhead power lines,
lateral profile.
Point No. |
Measurement height (m) |
Magnetic field level (µT) |
Frequency (Hz) |
ICNIRP General Public (%) |
|
0.3 |
0.17 |
37 |
0.13 |
1 (outdoor) |
1 |
0.17 |
21 |
0.07 |
|
1.5 |
0.11 |
9 |
0.02 |
|
0.3 |
0.20 |
20 |
0.08 |
2 (outdoor) |
1 |
0.22 |
28 |
0.12 |
|
1.5 |
0.11 |
31 |
0.07 |
|
0.3 |
0.16 |
25 |
0.08 |
3 (outdoor) |
1 |
0.18 |
15 |
0.06 |
|
1.5 |
0.13 |
48 |
0.13 |
Three-point
measurements at the location of interest (Residence).