Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP
General Public (%) |
|
Distance
from starting point (m) |
|||||
|
0.5 (above ground level) |
0.071 |
Resultant magnetic field |
50 |
0.071 |
2 |
1.0 (above ground level) |
0.108 |
Resultant magnetic field |
50 |
0.108 |
|
1.5 (above ground level) |
0.086 |
Resultant magnetic field |
50 |
0.086 |
|
- |
0.088 |
three-point average |
50 |
0.088 |
Starting
Point |
Measurement height (m) |
Electric field level (V/m) |
Field quantity |
Frequency (Hz) |
ICNIRP
General Public (%) |
Distance
from starting point (m) |
|||||
-2 |
1.0
(above ground level) |
220.636 |
Resultant
magnetic field |
50 |
4.413 |
Maximum magnetic and electric field values for
the investigated overhead power lines
Starting Point |
Measurement
height (m) |
Magnetic
field level (µT) |
Field
quantity |
Frequency
(Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
|
0.5 (above ground level) |
0.043 |
Resultant magnetic field |
50 |
0.043 |
1 |
1.0 (above ground level) |
0.013 |
Resultant magnetic field |
50 |
0.013 |
|
1.5 (above ground level) |
0.053 |
Resultant magnetic field |
50 |
0.053 |
|
- |
0.036 |
three-point average |
50 |
0.036 |
Starting Point |
Measurement
height (m) |
Electric
field level (V/m) |
Field
quantity |
Frequency
(Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
1 |
1.0 (above ground level) |
175.893 |
Resultant magnetic field |
50 |
3.518 |
Maximum magnetic and electric field values at the point of interest (plot at Giolou).
From the measurements performed it can be concluded that the:
·
Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.