Overhead Power Lines - Nicokleia, Paphos

Empty Lines

This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:

·         Overhead Power Lines “Pissouri - Kseropotamos”, Paphos, Tower 149 in close proximity to the investigated house at Nicokleia on the 15/10/2018 from 09:10 am until 10:30 am.

TThe measurements were performed according to the measurements of low-frequency magnetic and electric fields with regard to exposure of human beings (IEC 61786:1998) and measurement procedures with regard to public exposure (IEC 62110:2009). More specifically, the largest electric and magnetic field level is found under conductors at the point on the span where the conductors are closest to the ground. Therefore, the position where the field level is the maximum was found by first measuring at 1.0 m above the ground along the path parallel to the overhead line under conductors where possible at appropriate intervals (longitudinal profile), in the range of 5 Hz – 32 kHz using the EFA-300 Isotropic Field Analyser. Then, in order to discover whether anoter peak occurs, measurements were performed at 1.0 m above the ground along the path perpendicular to the overhead line, at the point of the longitudinal profile maximum (lateral profile).

In addition, three-point measurements were performed to assess the fields at the position of interest (assuming non-uniform fields). The measurements were performed at the position of interest at three heights 0.5 m, 1.0 m and 1.5 m. above the ground or floor level of the building. It is important to note that in this investigation additional point measurements were taken at locations indicated by the customer (nonstandardized measurements outside the measurement procedures with regard to public exposure (IEC 62110:2009).

The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respect to the recommended reference levels will ensure respect to the basic restrictions. The reference levels of exposure provided in 1999/519/EC are in accordance to the Cypriot Legislation.

The maximum magnetic and electric field values measured along the longitudinal and lateral profiles of the overhead power lines and at the location of interest are summarized in the following Tables.

Empty LinesEmpty Lines

     Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from

starting point (m)

-2 (Longitudinal)

1.0 (above ground level)

0.585

resultant magnetic field

50

0.585

-1 (Longitudinal)

1.0 (above ground level)

0.685

resultant magnetic field

50

0.685

0 (Longitudinal)

1.0 (above ground level)

0.636

resultant magnetic field

50

0.636

1 (Longitudinal)

1.0 (above ground level)

0.641

resultant magnetic field

50

0.641

2 (Longitudinal)

1.0 (above ground level)

0.345

resultant magnetic field

50

0.345

Starting Point

Measurement height (m)

Electric field level (V/m)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from starting point (m)

-2 (Lateral)

1.0 (above ground level)

1086.856

resultant magnetic field

50

21.737

-1 (Lateral)

1.0 (above ground level)

1354.141

resultant magnetic field

50

27.083

0 (Lateral)

1.0 (above ground level)

1516.160

resultant magnetic field

50

30.323

1 (Lateral)

1.0 (above ground level)

1584.243

resultant magnetic field

50

31.685

2 (Lateral)

1.0 (above ground level)

1580.432

resultant magnetic field

50

31.609

Maximum magnetic and electric field values for the investigated overhead power lines.

 

      Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from

starting point (m)

6

0.5 (above ground level)

0.025

resultant magnetic field

50

0.025

Kitchen (Indoors)

1.0 (above ground level)

0.022

resultant magnetic field

50

0.022

1.5 (above ground level)

0.014

resultant magnetic field

50

0.014

-

 

0.020

three-point average exposure level

50

0.020

Starting Point

Measurement height (m)

Electric field level (V/m)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from

starting point (m)

1 (Outdoors)

1.0 (above ground level)

633.512

resultant magnetic field

50

12.670

Maximum magnetic and electric field values at the point of interest (house at Nicokleia).

 



From the measurements performed it can be concluded that the:

·         Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC