Starting
Point |
Measurement
height (m) |
Magnetic
field level (µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP General Public
(%) |
Distance
from starting
point (m) |
|||||
-2 (Longitudinal) |
1.0
(above ground level) |
0.175 |
resultant magnetic field |
50 |
0.175 |
-1 (Longitudinal) |
1.0
(above ground level) |
0.160 |
resultant magnetic field |
50 |
0.160 |
0 (Longitudinal) |
1.0
(above ground level) |
0.151 |
resultant
magnetic field |
50 |
0.151 |
1 (Longitudinal) |
1.0
(above ground level) |
0.133 |
resultant
magnetic field |
50 |
0.133 |
2 (Longitudinal) |
1.0
(above ground level) |
0.043 |
resultant magnetic field |
50 |
0.043 |
Starting
Point |
Measurement
height (m) |
Electric
field level (V/m) |
Field
quantity |
Frequency (Hz) |
ICNIRP General Public
(%) |
Distance from starting
point (m) |
|||||
-2 (Lateral) |
1.0
(above ground level) |
794.140 |
resultant
electric field |
50 |
15.883 |
-1 (Lateral) |
1.0
(above ground level) |
1113.945 |
resultant
electric field |
50 |
22.279 |
0 (Lateral) |
1.0
(above ground level) |
1315.825 |
resultant
electric field |
50 |
26.317 |
1 (Lateral) |
1.0
(above ground level) |
1474.136 |
resultant
electric field |
50 |
29.483 |
2 (Lateral) |
1.0
(above ground level) |
1520.795 |
resultant
electric field |
50 |
30.416 |
Maximum
magnetic and electric field values for the investigated overhead power lines.
Starting
Point |
Measurement height (m) |
Magnetic
field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public
(%) |
Measuring point |
|||||
1 |
0.5
(above ground level) |
0.025 |
resultant
magnetic field |
50 |
0.025 |
1.0
(above ground level) |
0.030 |
resultant
magnetic field |
50 |
0.030 |
|
1.5
(above ground level) |
0.061 |
resultant
magnetic field |
50 |
0.061 |
|
- |
0.039 |
three-point average
exposure level |
50 |
0.039 |
Maximum magnetic field
values at the point of interest (plot at Agia Marinouda).
From the measurements performed it can be concluded that the:
·
Magnetic and electric field
measurements performed at the position of interest were below the recommended
General Public reference levels of the National Exposure Limits provided in
1999/519/EC