   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic
  field level
  (µT)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP
  General Public
  (%)  | 
 
| 
   Measuring
  point  | 
 |||||
| 
   Max Point  | 
  
   0.5
  (above ground level)  | 
  
   0.479  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.479  | 
 
| 
   1.0
  (above ground level)  | 
  
   0.332  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   0.338  | 
 |
| 
   1.5
  (above ground level)  | 
  
   0.182  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.182  | 
 |
| 
   -  | 
  
   0.331  | 
  
   three-point average exposure level  | 
  
   | 
  
   | 
 |
| 
   Starting Point 
 Distance from starting
  point (m)  | 
  
   Measurement
  height (m)  | 
  
   Electric
  field level (Vm)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP
  General Public (%)  | 
 
| 
   Max Point  | 
  
   1.0
  (above ground level)  | 
  
   
 99  | 
  
   0.05  | 
  
   1.30  | 
 
Maximum magnetic
and electric field values for the investigated underground power lines.
                                                              
| 
   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic
  field level
  (µT)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP
  General Public
  (%)  | 
 
| 
   Measuring
  point  | 
 |||||
| 
   P.3  | 
  
   0.5
  (above ground level)  | 
  
   0.021  | 
  
   resultant magnetic field  | 
  
   40  | 
  
   0.017  | 
 
| 
   1.0
  (above ground level)  | 
  
   0.023  | 
  
   resultant magnetic field  | 
  
   40  | 
  
   0.018  | 
 |
| 
   1.5
  (above ground level)  | 
  
   0.040  | 
  
   resultant
  magnetic field  | 
  
   35  | 
  
   0.028  | 
 |
| 
   -  | 
  
   0.028  | 
  
   three-point average exposure level  | 
  
   | 
  
   | 
 
Maximum magnetic field values at the location of
interest (plot).
From the measurements performed it can be concluded that the:
·        
	Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National  Exposure  Limits  provided in 1999/519/EC.