Starting
Point |
Measurement
height (m) |
Magnetic
field level
(µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP
General Public
(%) |
Measuring
point |
|||||
Max Point |
0.5
(above ground level) |
0.479 |
resultant magnetic field |
50 |
0.479 |
1.0
(above ground level) |
0.332 |
resultant magnetic field |
51 |
0.338 |
|
1.5
(above ground level) |
0.182 |
resultant magnetic field |
50 |
0.182 |
|
- |
0.331 |
three-point average exposure level |
|
|
|
Starting Point Distance from starting
point (m) |
Measurement
height (m) |
Electric
field level (Vm) |
Field
quantity |
Frequency (Hz) |
ICNIRP
General Public (%) |
Max Point |
1.0
(above ground level) |
99 |
0.05 |
1.30 |
Maximum magnetic
and electric field values for the investigated underground power lines.
Starting
Point |
Measurement
height (m) |
Magnetic
field level
(µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP
General Public
(%) |
Measuring
point |
|||||
P.3 |
0.5
(above ground level) |
0.021 |
resultant magnetic field |
40 |
0.017 |
1.0
(above ground level) |
0.023 |
resultant magnetic field |
40 |
0.018 |
|
1.5
(above ground level) |
0.040 |
resultant
magnetic field |
35 |
0.028 |
|
- |
0.028 |
three-point average exposure level |
|
|
Maximum magnetic field values at the location of
interest (plot).
From the measurements performed it can be concluded that the:
·
Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.