   Measurement height (m)  | 
  
  
   Magnetic field level (µT)  | 
  
  
   Field quantity  | 
  
  
   Frequency (Hz)  | 
  
  
   ICNIRP General Public (%)  | 
  
 |
| 
   Distance from starting point (m)  | 
  
 |||||
| 
   4  | 
  
  
   0.5 (above ground level)  | 
  
  
   3.257  | 
  
  
   resultant magnetic field  | 
  
  
   51  | 
  
  
   3.322  | 
  
 
| 
   1.0 (above ground level)  | 
  
  
   3.522  | 
  
  
   resultant magnetic field  | 
  
  
   50  | 
  
  
   3.522  | 
  
 |
| 
   1.5 (above ground level)  | 
  
  
   2.159  | 
  
  
   resultant magnetic field  | 
  
  
   50  | 
  
  
   2.159  | 
  
 |
| 
   -  | 
  
  
   2.979  | 
  
  
   three-point average  | 
  
  
   2.999  | 
  
 
Maximum
magnetic field values outside the substation, 0.2
m away from the left side boundary wall.
| 
   Starting Point  | 
  
   Measurement height (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1  | 
  
   0.5 (above ground level)  | 
  
   0.003  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0002  | 
 
| 
   Inside Apartment  | 
  
   1.0 (above ground level)  | 
  
   0.003  | 
  
   resultant magnetic field  | 
  
   7  | 
  
   0.0004  | 
 
| 
   (Balcony)  | 
  
   1.5 (above ground level)  | 
  
   0.003  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0003  | 
 
| 
   | 
  
   | 
  
   0.003  | 
  
   three-point average  | 
  
   | 
  
   0.0003  | 
 
| 
   2  | 
  
   0.5 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0002  | 
 
| 
   Inside Apartment  | 
  
   1.0 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0001  | 
 
| 
   (Kitchen)  | 
  
   1.5 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0001  | 
 
| 
   | 
  
   | 
  
   0.002  | 
  
   three-point average  | 
  
   | 
  
   0.0001  | 
 
| 
   3  | 
  
   0.5 (above ground level)  | 
  
   0.001  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0001  | 
 
| 
   Inside Apartment  | 
  
   1.0 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0002  | 
 
| 
   (Living Room)  | 
  
   1.5 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0001  | 
 
| 
   | 
  
   | 
  
   0.002  | 
  
   three-point average  | 
  
   | 
  
   0.0001  | 
 
| 
   4  | 
  
   0.5 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0002  | 
 
| 
   Outside Area
  Point A  | 
  
   1.0 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0001  | 
 
| 
   | 
  
   1.5 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   7  | 
  
   0.0003  | 
 
| 
   | 
  
   | 
  
   0.002  | 
  
   three-point average  | 
  
   | 
  
   0.0002  | 
 
| 
   5  | 
  
   0.5 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0001  | 
 
| 
   Outside Area
  Point B  | 
  
   1.0 (above ground level)  | 
  
   0.002  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0001  | 
 
| 
   | 
  
   1.5 (above ground level)  | 
  
   0.003  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0002  | 
 
| 
   | 
  
   | 
  
   0.002  | 
  
   three-point average  | 
  
   | 
  
   0.0002  | 
 
Maximum magnetic field values at the area of interest
(apartment and field).
From the measurements performed it can be concluded that the:
·        
	Magnetic field measurements performed at the area of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.