   Starting
  Point  | 
  
   Measurement height (m)  | 
  
   Magnetic
  field level (µT)  | 
  
   Field quantity  | 
  
   Frequency
  (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Distance
  from starting
  point (m)  | 
 |||||
| 
   1  | 
  
   0.5
  (above ground level)  | 
  
   0.214  | 
  
   Resultant
  magnetic field  | 
  
   50  | 
  
   0.214  | 
 
| 
   1.0
  (above ground level)  | 
  
   0.212  | 
  
   Resultant
  magnetic field  | 
  
   50  | 
  
   0.212  | 
 |
| 
   1.5
  (above ground level)  | 
  
   0.076  | 
  
   Resultant
  magnetic field  | 
  
   50  | 
  
   0.076  | 
 |
| 
   -  | 
  
   0.168  | 
  
   three-point
  average  | 
  
   50  | 
  
   0.168  | 
 
Maximum magnetic field values
outside the substation, 0.2 m away from the rear side
boundary wall.
| 
   Starting
  Point  | 
  
   Measurement height (m)  | 
  
   Magnetic
  field level (µT)  | 
  
   Field quantity  | 
  
   Frequency
  (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   5  | 
  
   0.5
  (above ground level)  | 
  
   0.003  | 
  
   Resultant
  magnetic field  | 
  
   50  | 
  
   0.003  | 
 
| 
   1.0
  (above ground level)  | 
  
   0.007  | 
  
   Resultant
  magnetic field  | 
  
   50  | 
  
   0.007  | 
 |
| 
   1.5
  (above ground level)  | 
  
   0.009  | 
  
   Resultant
  magnetic field  | 
  
   50  | 
  
   0.009  | 
 |
| 
   -  | 
  
   0.006  | 
  
   three-point
  average  | 
  
   50  | 
  
   0.006  | 
 
Maximum magnetic field values at the location of
interest (plot).
From the measurements performed it can be concluded that the:
·        
	Magnetic field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.