Starting
Point |
Measurement height (m) |
Magnetic
field level (µT) |
Field quantity |
Frequency
(Hz) |
ICNIRP General Public (%) |
Distance
from starting
point (m) |
|||||
1 |
0.5
(above ground level) |
0.214 |
Resultant
magnetic field |
50 |
0.214 |
1.0
(above ground level) |
0.212 |
Resultant
magnetic field |
50 |
0.212 |
|
1.5
(above ground level) |
0.076 |
Resultant
magnetic field |
50 |
0.076 |
|
- |
0.168 |
three-point
average |
50 |
0.168 |
Maximum magnetic field values
outside the substation, 0.2 m away from the rear side
boundary wall.
Starting
Point |
Measurement height (m) |
Magnetic
field level (µT) |
Field quantity |
Frequency
(Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
5 |
0.5
(above ground level) |
0.003 |
Resultant
magnetic field |
50 |
0.003 |
1.0
(above ground level) |
0.007 |
Resultant
magnetic field |
50 |
0.007 |
|
1.5
(above ground level) |
0.009 |
Resultant
magnetic field |
50 |
0.009 |
|
- |
0.006 |
three-point
average |
50 |
0.006 |
Maximum magnetic field values at the location of
interest (plot).
From the measurements performed it can be concluded that the:
·
Magnetic field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.