Substation - Substation 5131, Vasilopoullos Court

 

On the 14th of April 2006 at 11:00 am, magnetic field measurements were performed for Substation 5131. The substation of interest is located in the basement of Vasilopoullos Court on Strovolos avenue in Nicosia.

vassilopoulos.jpg ss5131.jpg

The substation is rated at a nominal power of 1000 KVA. At the time when the measurements were performed, the substation load power was recorded as:

Red Phase

Yellow Phase

Blue Phase

160A

170A

160A

Table 1:  Measured load current

The resultant load of all three phases was 12% utilization of the nominal load current.

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organizations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 2: ICNIRP exposure limits for Occupational and General Public exposure

The obtained results for the RMS fields inside and outside the substation are shown in tables 3 and 4 respectively and a comparison is made with the ICNIRP recommendations.

Substation 5131 Vasilopoullos: Fields Inside Substation

Distance from Side (m)

Maximum Magnetic Field (µT) at Z Height (m)
Percentage of ICNIRP Occupational Standard (%)

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Inside SubStation Field Measurements (Distance from Front Inside Wall)

0m from Front Side

2.19

0.44%

2.72

0.54%

2.15

0.43%

0.5m from Front Side

10.51

2.10%

20.37

4.07%

14.26

2.85%

1m from Front Side

13.42

2.68%

24.53

4.91%

17.81

3.56%

1.5m from Front Side

80.51

16.10%

344.59

68.92%

239.13

47.83%

2m from Front Side

164.50

32.90%

90.61

18.12%

49.07

9.81%

2.5m from Front Side

82.86

16.57%

241.68

48.34%

19.79

3.96%

3m from Front Side

153.61

30.72%

159.54

31.91%

63.84

12.77%

Table 3: Maximum field measurements inside Substation 5131

Substation 5131 Vasilopoullos: Fields outside the Substation

Distance from Side (m)

Maximum Magnetic Field (μT) at Z Height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

SubStation Front Side Field Measurements

0m from Front Side

--

--

0.93

0.93%

--

--

1m from Front Side

--

--

0.21

0.21%

--

--

Substation Left Side Field Measurements (EAC Room)

In front of
Main Switch Board

--

--

72.5

72.5%

--

--

Table 4: Maximum field measurements outside Substation 5131


Parking area / office above Substation 5131

The parking area and office of Vasilopoullos Court are situated above Substation 5131, on the right side when facing the Vasilopoullos building.

Field measurements for this apartment were performed on the 14th of April 2006 at 12:00pm.

The obtained results for the RMS magnetic fields inside the referenced parking area and office are shown in table 5 and a comparison is made with the ICNIRP recommendations.

Parking area / office above SS 5131: Maximum field measurements

Distance from Side (m)

Maximum Magnetic Field (µT) at Z Height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Parking Area Field Measurements from Left Side of Parking Area (above Substation)

0m from Left Side

0.84

0.84%

0.50

0.50%

0.41

0.41%

1m from Left Side

1.31

1.31%

0.67

0.67%

0.43

0.43%

2m from Left Side

1.54

1.54%

0.66

0.66%

0.41

0.41%

3m from Left Side

1.36

1.36%

0.57

0.57%

0.34

0.34%

Office Inside Field Measurements from Office Front Side

0m from Front Side

--

--

0.30

0.30%

--

--

1m from Front Side

--

--

0.26

0.26%

--

--

3m from Front Side

--

--

0.16

0.16%

--

--

5m from Front Side

--

--

0.15

0.15%

--

--

7m from Front Side

--

--

0.19

0.19%

--

--

Table 5: Maximum field measurements in the parking area and office above Substation 5131