Substation - Substation 3974, Byzantium Gardens

 

On the 2nd of March 2007 at 9:00 am magnetic field measurements were performed for Substation 3974 Byzantium Gardens. The substation of interest is located on the basement of the Byzantium Gardens building, Byzantiou Street in Nicosia.

ss3974.jpg ss3974right.jpg

The substation is rated at a nominal power of 500 KVA. At the time when the measurements were performed, the substation load power was recorded as:


Red Phase

Yellow Phase

Blue Phase

370A

340A

390A

Table 1: Measured load current


The resultant load of all three phases was 33% utilization of the nominal load current.

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organizations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 2: ICNIRP Exposure limits for Occupational and General Public exposure

The obtained results for the RMS fields inside and outside the substation are shown in tables 3 and 4 respectively. A comparison is also made with the ICNIRP recommendations.

Inside Field Measurements

Distance from Side /m

Maximum Magnetic Field at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

Plot Field Measurements

0m from Front Side

3.93

0.79%

3.06

0.61%

2.76 

0.55%

0.5m from Front Side

7.40

1.48%

5.65 

1.13%

6.30 

1.26%

1m from Front Side

13.79

2.76%

14.08 

2.82%

13.82 

2.76%

1.5m from Front Side

156.44

31.29%

161.49 

32.30%

23.24 

4.65%

2m from Front Side

64.43

12.89%

64.58 

12.92%

41.36 

8.27%

2.5m from Front Side

174.62

34.92%

182.24 

36.45%

86.48 

17.30%

Table 3: Magnetic Field Measurements inside area

Outside Field Measurements

Distance from Side /m

Maximum Magnetic Field at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

Plot Field Measurements

0m from Front Side

2.18

2.18%

1.84 

1.84%

1,45 

1.45%

1m  from Front side

0.75

0.75%

0.77

0.77%

0.61

0.61%

Substation Front Side

0m from Right Side

3.24

3.24%

1.66

1.66%

0.77 

0.77%

1m from Right Side

1.34 

1.34%

0.94

0.94%

0.58

0.58%

2m from Right Side

0.89

0.89%

0.62

0.62%

0.44

0.44%

Table 4: Magnetic Field Measurements in the outside area