Substation - Substation 3236, Dhmosthenous Severi

 

On the 27th of April 2007 at 9:00 am magnetic field measurements were performed for Substation 3236 Dhmosthenous Severi. The substation of interest is located on Spyridonos Lambrou Street in Nicosia.

severi.jpg ss3236.jpg

The substation is rated at a nominal power of 1000 KVA. At the time when the measurements were performed, the substation load power was recorded as:

Red Phase

Yellow Phase

Blue Phase

330A

270A

330A

Table 1:  Measured Load Current


The resultant load of all three phases was 22% utilisation of the nominal load current.

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 2: ICNIRP Exposure limits for Occupational and General Public exposure

The obtained results for the fields inside and outside the substation are shown in tables 3 and 4 respectively and a comparison is made with the ICNIRP recommendations.

Substation 3236 Dhmosthenous Severi: Fields inside substation

Distance from Side /m

Maximum Magnetic Field / µT at Z Height /m  -
Percentage of ICNIRP Occupational Standard /%

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Inside Substation Field Measurements (Distance from Left Inside Wall)

0m from Left Side

54,31

10,86%

92,05

18,41%

23,18

4,64%

0.5m from Left Side

96,02

19,20%

35,03

7,01%

14,03

2,81%

1m from Left Side

5,84

1,17%

14,50

2,90%

3,81

0,76%

1.5m from Left Side

4,92

0,98%

4,85

0,97%

6,19

1,24%

2m from Left Side

2,47

0,49%

2,69

0,54%

2,47

0,49%

2.5m from Left Side

4,34

0,87%

1,74

0,35%

2,35

0,47%

3m from Left Side

4,54

0,91%

7,76

1,55%

6,43

1,29%

3.5m from Left Side

4,35

0,87%

11,07

2,21%

14,90

2,98%

4m from Left Side

0,76

0,15%

0,87

0,17%

1,61

0,32%

4.5m from Left Side

54,31

10,86%

92,05

18,41%

23,18

4,64%

5m from Left Side

96,02

19,20%

35,03

7,01%

14,03

2,81%

Table 3: Maximum field measurements inside substation 3236

Substation 3236 Dhmosthenous Severi: Fields Outside Substation

Distance from Side /m

Maximum Magnetic Field / µT at Z Height /m  -
Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Substation Front Side Field Measurements

Point A

 

 

0,34

0,34%

 

 

Point B

 

 

0,50

0,50%

 

 

Point C

 

 

0,33

0,33%

 

 

Parking Area Field Measurements

0m from Left Side

0,56

0,56%

0,26

0,26%

0,17

0,17%

2m from Left Side

0,58

0,58%

0,24

0,24%

0,16

0,16%

4m from Left Side

0,35

0,35%

0,18

0,18%

0,12

0,12%

Table 4: Maximum field measurements outside substation 3236