Substation - Substation 3136, Alexandrou Ypsilanti

 

On the 23rd of October 2006 at 10:00am, magnetic field measurements were performed for Substation 3136 Alexandrou Ypsilanti. The substation of interest is located in an area along the main road of Latsia towards Geri in Nicosia.

ypsilanti1.jpg ypsilanti3136.jpg

The substation is rated at a nominal power of 315 KVA. At the time when the measurements were performed, the substation load power was recorded as:

Red Phase

Yellow Phase

Blue Phase

60A

50A

40A

Table 1:  Measured Load Current


The resultant load of all three phases was 11% utilisation of the nominal load current.

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 2: ICNIRP Exposure limits for Occupational and General Public exposure

The obtained results for the fields inside and outside the substation are shown in tables 3 and 4 respectively and a comparison is made with the ICNIRP recommendations.

Substation 3136 Alexandrou Ypsilanti: Fields Inside Substation

Distance from Side (m)

Maximum Magnetic Field (µT) at Z Height (m)
Percentage of ICNIRP Occupational Standard (%)

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Inside Substation Field Measurements (Distance from left inside wall)

0m from Left Side

29,52

5,90%

40,54

8,11%

25,84

5,17%

0.5m from Left Side

14,55

2,91%

19,39

3,88%

25,04

5,01%

1m from Left Side

12,90

2,58%

9,54

1,91%

15,95

3,19%

1.5m from Left Side

11,27

2,25%

4,71

0,94%

2,95

0,59%

2m from Left Side

32,01

6,40%

13,25

2,65%

6,19

1,24%

2.5m from Left Side

228,93

45,79%

63,82

12,76%

2,76

0,55%

3m from Left Side

7,23

1,45%

7,97

1,59%

3,72

0,74%

3.5m from Left Side

1,82

0,36%

1,25

0,25%

0,84

0,17%

Table 3: Maximum field measurements inside substation 3136

 

Substation 3136 Alexandrou Ypsilanti: Fields Outside Substation

Distance from Side (m)

Maximum Magnetic Field (µT) at Z Height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Substation Front Side Field Measurements

0m from Front Side

0,58

0,58%

0,65

0,65%

0,62

0,62%

1m from Front Side

0,59

0,59%

0,51

0,51%

0,51

0,51%

Substation Left Side Field Measurements

0m from Left Side

3,29

3,29%

5,70

5,70%

7,08

7,08%

1m from Left Side

0,62

0,62%

1,12

1,12%

1,74

1,74%

Substation Right Side Field Measurements

0m from Right Side

0,41

0,41%

0,62

0,62%

0,55

0,55%

1m from Right Side

0,45

0,45%

0,46

0,46%

0,49

0,49%

Substation Back Side Field Measurements

0m from Back Side

0,37

0,37%

0,31

0,31%

0,34

0,34%

1m from Back Side

0,34

0,34%

0,34

0,34%

0,36

0,36%

Table 4: Maximum field measurements outside substation 3136