Substation - Substation 3087, Akritas Tower

 

On the 17th of March 2006 at 11:30am, electric and magnetic field measurements were performed on Substation 3087 at Akritas Tower. This substation is located on the ground floor of the Akritas Tower building, Kleomenous street in Nicosia.

akritas.jpg ss3087.jpg

The substation is rated at a nominal power of 1000 KVA but the maximum observed values during the year were usually not greater than 800KVA.
At the time when the measurements were performed, the substation load power was recorded as:

Red Phase

Yellow Phase

Blue Phase

400A

370A

400A

Table 1: Measured load current

The resultant load of all three phases was 28% utilization of the nominal load current.

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organizations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 2: ICNIRP exposure limits for occupational and general public exposure

The obtained results for the RMS fields inside and outside the substation are shown in tables 3 and 4 respectively, and a comparison is made with the ICNIRP recommendations.

Substation 3087 Akritas Tower: Fields inside the substation

Field Description

Position at height 1m

Value (µT)

ICNIRP
Occupational Standard (%)

Magnetic Field (µT)

In front of Pindaros switch at a distance of 0m

1,462

0,29%

In front of Geogkas-Krentos switch at a distance of 0m

15,57

3,11%

In front of Sofoklhs Hliadhs supply at a distance of 0m

41,96

8,39%

In front of L.V. pillar fuses at a distance of 0m

84,24

16,85%

In front of L.V. pillar bus bar at a distance of 0m

329,1

65,82%

In front of transformer 415V Cables at a distance of 0m

543,2

108,64%

In front of transformer 11,000V Cables at a distance of 0m  

14,9

2,98%

In front of cables entering the SS at a distance of 0m

17,55

3,51%

Table 3: Maximum field strength measurements inside Substation 3087

Substation 3087 Akritas Tower: Fields outside the substation

Distance from side (m)

Maximum Magnetic Field (µT) at Z Height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Substation front side field measurements

0m from front side

--

--

0,494

0,49%

--

--

Substation left side field measurements

0m from left side

1,0022

1,00%

0,5286

0,53%

0,27653

0,28%

1m from left side

0,55406

0,55%

0,33297

0,33%

0,23837

0,24%

2m from left side

0,34769

0,35%

0,25687

0,26%

0,19956

0,20%

Substation right side field measurements

0m from right side

15,2

15.20%

--

--

--

--

1m from right side

9,6423

9,64%

7,4602

7,46%

3,3841

3,38%

2.5m from right side

1,8094

1,81%

1,3242

1,32%

1,06

1,06%

Table 4: Maximum field strength measurements outside Substation 3087

Shop No.3, above the substation

Shop No.3 of Akritas Tower is situated on the ground floor of the building, directly above Substation 3087. Field measurements for this shop were performed on the 17th of March 2006 at 12:30pm.

The obtained measurements for the RMS fields strength inside and outside the referenced shop are shown in tables 5 and 6 respectively and a comparison is made with the ICNIRP recommendations.

Shop Above Substation 3087: Maximum field measurements inside the shop

Distance from side (m)

Maximum magnetic field (µT) at Z height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

Shop's inside field measurements from front side obstacle

0m from obstacle 1

1,5634

1,56%

0,74794

0,75%

0,42218

0,42%

2m from obstacle 1

1,2798

1,28%

0,52198

0,52%

0,27011

0,27%

3.5m from obstacle 1

0,6764

0,68%

0,24153

0,24%

0,26928

0,27%

Shop's inside field measurement points A, B, C and D

Point A

0,246

0,25%

--

--

--

--

Point B

0,255

0,26%

--

--

--

--

Point C

0,646

0,65%

--

--

--

--

Point D

0,191

0,19%

--

--

--

--

Table 5: Maximum field strength measurements inside the shop, above Substation 3087

Shop above Substation 3087: Maximum field measurements outside

Distance from side (m)

Maximum magnetic field (µT) at Z height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

Shop's front side field measurements

0m from front side

0,66571

0,67%

0,43626

0,44%

0,70159

0,70%

2m from front side

0,55319

0,55%

0,31736

0,32%

0,26542

0,27%

4m from front side

0,82865

0,83%

0,40085

0,40%

0,29168

0,29%

Shop's left side field measurements

0m from left side

0,47679

 

 

 

 

 

Shop's back side field measurements

0m from back side

 

 

 

 

 

 

Table 6: Maximum field strength measurements outside the shop, above Substation 3087