Overhead Power Lines - Meniko, Nicosia

Empty Lines

This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:

·         Overhead Power Lines “Ergates – Orounta – Kokkinotrimithia” in close proximity to the investigated area, Plot at Meniko, Nicosia, on the 09/02/2021 from 11:30 until 13:00.

The measurements were performed according to the measurements of low-frequency magnetic and electric fields with regard to exposure of human beings (IEC 61786:1998) and measurement procedures with regard to public exposure (IEC 62110:2009). More specifically, the largest electric and magnetic field level is found under conductors at the point on the span where the conductors are closest to the ground. Therefore, the position where the field level is the maximum was found by first measuring at 1.0 m above the ground along the path parallel to the overhead line under conductors where possible at appropriate intervals (longitudinal profile), in the range of 5 Hz – 32 kHz using the EFA-300 Isotropic Field Analyser. Then, in order to discover whether anoter peak occurs, measurements were performed at 1.0 m above the ground along the path perpendicular to the overhead line, at the point of the longitudinal profile maximum (lateral profile).

It is important to note that in this investigation additional point measurements were taken at locations indicated by the customer (non-standardized measurements outside the measurement procedures with regard to public exposure (IEC 62110:2009).The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respect to the recommended reference levels will ensure respect to the basic restrictions. The reference levels of exposure provided in 1999/519/EC are in accordance to the Cypriot Legislation.

The maximum magnetic and electric field values measured along the longitudinal and lateral profiles of the overhead power lines and at the location of interest are summarized in the following Tables.

Empty LinesEmpty Lines

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from starting point (m)

-2

1.0 (above ground level)

0.170

resultant magnetic field

51

0.173

-1

1.0 (above ground level)

0.174

resultant magnetic field

50

0.174

0

1.0 (above ground level)

0.175

resultant magnetic field

50

0.175

1

1.0 (above ground level)

0.174

resultant magnetic field

50

0.174

2

1.0 (above ground level)

0.168

resultant magnetic field

50

0.168

Starting Point

Measurement height (m)

Electric field level (V/m)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from starting point (m)

-2

1.0 (above ground level)

1854.400

resultant magnetic field

50

37.088

-1

1.0 (above ground level)

2032.400

resultant magnetic field

50

40.648

0

1.0 (above ground level)

2108.400

resultant magnetic field

51

43.011

1

1.0 (above ground level)

2092.500

resultant magnetic field

50

41.850

2

1.0 (above ground level)

2057.700

resultant magnetic field

51

41.977

Maximum magnetic and electric field values for the investigated overhead power lines.

 

Plot at Meniko, Nicosia

Measurement height (m)

Magnetic

field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Measurement Point

1

1.0 (above ground level)

0.006

resultant magnetic field

5

0.001

2

1.0 (above ground level)

0.010

resultant magnetic field

5

0.001

3

1.0 (above ground level)

0.012

resultant magnetic field

10

0.002

4

1.0 (above ground level)

0.069

resultant magnetic field

50

0.069

Maximum magnetic field values at the point of interest (Plot at Meniko, Nicosia).

From the measurements performed it can be concluded that the:

·         Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.