   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic
  field level (µT)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public
  (%)  | 
 
| 
   Distance
  from starting
  point (m)  | 
 |||||
| 
   -2 (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.607  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.607  | 
 
| 
   -1 (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.523  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.523  | 
 
| 
   0 (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.051  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   0.051  | 
 
| 
   1 (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.568  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   0.568  | 
 
| 
   2 (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.508  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.508  | 
 
| 
   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Electric
  field level (V/m)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public
  (%)  | 
 
| 
   Distance from starting
  point (m)  | 
 |||||
| 
   -2 (Longitudinal)  | 
  
   1.0
  (above ground level)  | 
  
   2100.273  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   42.005  | 
 
| 
   -1 (Longitudinal)  | 
  
   1.0
  (above ground level)  | 
  
   2123.242  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   42.465  | 
 
| 
   0 (Longitudinal)  | 
  
   1.0
  (above ground level)  | 
  
   2152.082  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   43.042  | 
 
| 
   1 (Longitudinal)  | 
  
   1.0
  (above ground level)  | 
  
   2156.614  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   43.132  | 
 
| 
   2 (Longitudinal)  | 
  
   1.0
  (above ground level)  | 
  
   2189.265  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   43.785  | 
 
Maximum
magnetic and electric field values for the investigated overhead power lines.
| 
   Starting
  Point  | 
  
   Measurement height (m)  | 
  
   Magnetic
  field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public
  (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1 (Outdoor)  | 
  
   0.5
  (above ground level)  | 
  
   0.002  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   0.002  | 
 
| 
   1.0
  (above ground level)  | 
  
   0.001  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   0.001  | 
 |
| 
   1.5
  (above ground level)  | 
  
   0.004  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.004  | 
 |
| 
   -  | 
  
   0.002  | 
  
   three-point average
  exposure level  | 
  
   50  | 
  
   0.002  | 
 
Maximum
magnetic field values at the point of interest (plot at Agious
Trimithias, Nicosia).
From the measurements performed it can be concluded that the:
·        
	Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.