Starting
Point |
Measurement
height (m) |
Magnetic
field level (µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP General Public
(%) |
|
Distance
from starting
point (m) |
|||||
|
-2
(Longitudinal) |
1.0
(above ground level) |
0.543 |
resultant
magnetic field |
50 |
0.543 |
|
-1
(Longitudinal) |
1.0
(above ground level) |
0.452 |
resultant magnetic field |
50 |
0.452 |
|
0
(Longitudinal) |
1.0
(above ground level) |
0.545 |
resultant magnetic field |
50 |
0.545 |
|
1
(Longitudinal) |
1.0
(above ground level) |
0.570 |
resultant magnetic field |
50 |
0.570 |
|
2 (Longitudinal) |
1.0
(above ground level) |
0.453 |
resultant
magnetic field |
50 |
0.453 |
|
Starting
Point |
Measurement
height (m) |
Electric
field level (V/m) |
Field quantity |
Frequency (Hz) |
ICNIRP General
Public (%) |
|
Distance from starting
point (m) |
|||||
|
-2
(Lateral) |
1.0
(above ground level) |
1683.947 |
resultant
electric field |
50 |
33.679 |
|
-1
(Lateral) |
1.0
(above ground level) |
1612.465 |
resultant
electric field |
50 |
32.249 |
|
0
(Lateral) |
1.0
(above ground level) |
1449.004 |
resultant
electric field |
50 |
28.980 |
|
1
(Lateral) |
1.0
(above ground level) |
1293.680 |
resultant
electric field |
50 |
25.874 |
|
2
(Lateral) |
1.0
(above ground level) |
1119.404 |
resultant
electric field |
50 |
22.388 |
Maximum
magnetic and electric field values for the investigated overhead power lines.
|
Starting
Point |
Measurement
height (m) |
Magnetic
field level (µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP General Public
(%) |
|
Measuring point |
|||||
|
1 (Outdoors) |
0.5 (above ground level) |
0.014 |
resultant magnetic field |
50 |
0.014 |
|
1.0 (above ground level) |
0.009 |
resultant magnetic field |
50 |
0.009 |
|
|
1.5 (above ground level) |
0.023 |
resultant magnetic field |
50 |
0.023 |
|
|
- |
0.015 |
three-point
average exposure level |
50 |
0.015 |
Maximum magnetic field values at the point of
interest (house at Peristerona).
From the measurements performed it can be concluded that the:
·
Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.