   Starting
  Point  | 
  
   Measurement height
  (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Distance from starting point
  (m)  | 
 |||||
| 
   3  | 
  
   0.5 (above ground
  level)  | 
  
   0.086  | 
  
   resultant magnetic field  | 
  
   16  | 
  
   0.027  | 
 
| 
   1.0 (above ground
  level)  | 
  
   0.152  | 
  
   resultant magnetic field  | 
  
   46  | 
  
   0.140  | 
 |
| 
   1.5 (above ground
  level)  | 
  
   0.168  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   0.172  | 
 |
| 
   -  | 
  
   0.135  | 
  
   three-point average exposure level  | 
  
   | 
  
   | 
 
Maximum magnetic
field values outside the substation, 0.2 m away from the left
side boundary wall.
| 
   Starting Point  | 
  
   Measurement height
  (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1 (Rear
  Yard)  | 
  
   1.0 (above ground
  level)  | 
  
   0.003  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0002  | 
 
Maximum magnetic
field values at the area of
interest (House, back yard).
From the measurements performed it can be concluded that the:
·        
	Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.