Starting
Point |
Measurement height
(m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from starting point
(m) |
|||||
3 |
0.5 (above ground
level) |
0.086 |
resultant magnetic field |
16 |
0.027 |
1.0 (above ground
level) |
0.152 |
resultant magnetic field |
46 |
0.140 |
|
1.5 (above ground
level) |
0.168 |
resultant magnetic field |
51 |
0.172 |
|
- |
0.135 |
three-point average exposure level |
|
|
Maximum magnetic
field values outside the substation, 0.2 m away from the left
side boundary wall.
Starting Point |
Measurement height
(m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
1 (Rear
Yard) |
1.0 (above ground
level) |
0.003 |
resultant magnetic field |
5 |
0.0002 |
Maximum magnetic
field values at the area of
interest (House, back yard).
From the measurements performed it can be concluded that the:
·
Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.