   Starting Point  | 
  
   Measurement height
  (m)  | 
  
   Magnetic field level
  (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Distance
  from starting point
  (m)  | 
 |||||
| 
   3  | 
  
   0.5 (above
  ground level)  | 
  
   2.005  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   2.005  | 
 
| 
   1.0 (above ground
  level)  | 
  
   3.030  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   3.030  | 
 |
| 
   1.5 (above ground
  level)  | 
  
   4.413  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   4.413  | 
 |
| 
   -  | 
  
   3.149  | 
  
   three-point average exposure level  | 
  
   | 
  
   | 
 
Maximum
magnetic field values outside
the substation, 0.2 m away from the front side boundary wall.
| 
   Starting
  Point  | 
  
   Measurement height
  (m)  | 
  
   Magnetic field level
  (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1 (Kitchen, ground fl.)  | 
  
   1.0 (above ground
  level)  | 
  
   0.007  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0004  | 
 
| 
   2 (Bedroom, first fl.)  | 
  
   1.0 (above
  ground level)  | 
  
   0.006  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0004  | 
 
Maximum
magnetic field values at the
area of interest (House).
From the measurements performed it can be concluded that the:
·        
	Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.