Starting Point |
Measurement height
(m) |
Magnetic field level
(µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance
from starting point
(m) |
|||||
3 |
0.5 (above
ground level) |
2.005 |
resultant magnetic field |
50 |
2.005 |
1.0 (above ground
level) |
3.030 |
resultant magnetic field |
50 |
3.030 |
|
1.5 (above ground
level) |
4.413 |
resultant magnetic field |
50 |
4.413 |
|
- |
3.149 |
three-point average exposure level |
|
|
Maximum
magnetic field values outside
the substation, 0.2 m away from the front side boundary wall.
Starting
Point |
Measurement height
(m) |
Magnetic field level
(µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
1 (Kitchen, ground fl.) |
1.0 (above ground
level) |
0.007 |
resultant magnetic field |
5 |
0.0004 |
2 (Bedroom, first fl.) |
1.0 (above
ground level) |
0.006 |
resultant magnetic field |
5 |
0.0004 |
Maximum
magnetic field values at the
area of interest (House).
From the measurements performed it can be concluded that the:
·
Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.