Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from starting point (m) |
|||||
3 |
0.5 (above ground level) |
0.134 |
resultant
magnetic field |
50 |
0.134 |
1.0 (above ground level) |
0.160 |
resultant
magnetic field |
50 |
0.160 |
|
1.5 (above ground level) |
0.181 |
resultant
magnetic field |
50 |
0.181 |
|
- |
0.158 |
three-point
average exposure level |
|
|
Maximum magnetic field values outside the
substation, 0.2 m away from the left side boundary wall.
Starting
Point |
Measurement
height (m) |
Magnetic field level (µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
1 |
1.0 (above ground level) |
0.005 |
resultant magnetic field |
6 |
0.0004 |
2 |
1.0 (above ground level) |
0.003 |
resultant
magnetic field |
5 |
0.0002 |
3 |
1.0 (above ground level) |
0.004 |
resultant
magnetic field |
6 |
0.0003 |
4 |
1.0 (above ground level) |
0.003 |
resultant
magnetic field |
9 |
0.0006 |
Maximum
magnetic field values at the area of interest (Plot No.1).
From the measurements performed it can be concluded that the:
·
Magnetic field measurements performed at the area of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.