This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the area of interest:

·         Substation S/S «ATTIKI STR.» in direct proximity with house at Attikis Street, Strovolos, Nicosia, on the 20/12/2021 from 11:15 until 12:00.

The measurements were performed according to the measurements of low-frequency magnetic and electric fields with regard to exposure of human beings (IEC 61786:1998) and measurement procedures with regard to public exposure (IEC 62110:2009). More specifically, three-point measurements were performed to assess the fields (assuming non-uniform fields) in the range of 5 Hz – 32 kHz using the EFA-300 Isotropic Field Analyser. The measurements were performed at the position of interest at three heights 0.5 m, 1.0 m and 1.5 m. above the ground or floor level of the building. Beside power equipment or in a building, measurement was performed at a horizontal distance of 0.2 m from its surface or boundary wall. It is important to note that in this investigation additional point measurements were taken at locations indicated by the customer (non-standardized measurements outside the measurement procedures with regard to public exposure (IEC 62110:2009).

The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respect to the recommended reference levels will ensure respect to the basic restrictions. The reference levels of exposure provided in 1999/519/EC are in accordance to the Cypriot Legislation.

The maximum magnetic field values measured at the area of interest are summarized in the following Tables.

Empty LinesEmpty Lines

Starting Point

Measurement height (m)

   Magnetic field     level (µT)

Field quantity

Frequency (Hz)

ICNIRP

    Genera

   Public(%)

Distance from starting point (m)

3.5

0.5 (above ground level)

6.195

resultant magnetic field

50

6.1952

1.0 (above ground level)

6.043

resultant magnetic field

50

6.0428

1.5 (above ground level)

1.237

resultant magnetic field

51

1.2616

-

4.492

three-point average exposure level

-

-

Maximum magnetic field values outside the substation, 0.2 m away from the left side boundary wall.

 

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Measuring point

1 (rear outdoor yard)

1.0 (above ground level)

0.024

resultant magnetic field

5

0.0015

Maximum magnetic field values at the area of interest (Plot No.1).

From the measurements performed it can be concluded that the:

·         Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.