   Starting Point  | 
  
   Measurement height (m)  | 
  
      Magnetic field     level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP     Genera    Public(%)  | 
 
| 
   Distance
  from starting point (m)  | 
 |||||
| 
   3.5  | 
  
   0.5 (above ground level)  | 
  
   6.195  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   6.1952  | 
 
| 
   1.0 (above ground level)  | 
  
   6.043  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   6.0428  | 
 |
| 
   1.5 (above ground level)  | 
  
   1.237  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   1.2616  | 
 |
| 
   -  | 
  
   4.492  | 
  
   three-point average
  exposure level  | 
  
   -  | 
  
   -  | 
 
Maximum magnetic field values outside the
substation, 0.2 m away from the left side boundary wall.
| 
   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General
  Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1 (rear outdoor yard)  | 
  
   1.0 (above ground level)  | 
  
   0.024  | 
  
   resultant magnetic field  | 
  
   5  | 
  
   0.0015  | 
 
Maximum
magnetic field values at the area of interest (Plot No.1).
From the measurements performed it can be concluded that the:
·        
	Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.