Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP Genera Public(%) |
Distance
from starting point (m) |
|||||
3.5 |
0.5 (above ground level) |
6.195 |
resultant magnetic field |
50 |
6.1952 |
1.0 (above ground level) |
6.043 |
resultant magnetic field |
50 |
6.0428 |
|
1.5 (above ground level) |
1.237 |
resultant magnetic field |
51 |
1.2616 |
|
- |
4.492 |
three-point average
exposure level |
- |
- |
Maximum magnetic field values outside the
substation, 0.2 m away from the left side boundary wall.
Starting
Point |
Measurement
height (m) |
Magnetic field level (µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP General
Public (%) |
Measuring point |
|||||
1 (rear outdoor yard) |
1.0 (above ground level) |
0.024 |
resultant magnetic field |
5 |
0.0015 |
Maximum
magnetic field values at the area of interest (Plot No.1).
From the measurements performed it can be concluded that the:
·
Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.