   Starting
  Point  | 
  
   Measurement height
  (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Distance from starting point
  (m)  | 
 |||||
| 
   3  | 
  
   0.5 (above ground
  level)  | 
  
   28.483  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   29.053  | 
 
| 
   1.0 (above ground
  level)  | 
  
   54.677  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   55.771  | 
 |
| 
   1.5 (above ground
  level)  | 
  
   61.120  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   62.343  | 
 |
| 
   -  | 
  
   48.094  | 
  
   three-point average exposure level  | 
  
   | 
  
   | 
 
Maximum magnetic field values outside the substation, 0.2 m away from the left
side boundary wall.
| 
   Starting Point  | 
  
   Measurement height
  (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1 (Kitchen, ground fl.)  | 
  
   1.0 (above ground
  level)  | 
  
   0.024  | 
  
   resultant magnetic field  | 
  
   37  | 
  
   0.0180  | 
 
| 
   2 (Bedroom, first fl.)  | 
  
   1.0 (above
  ground level)  | 
  
   0.030  | 
  
   resultant magnetic field  | 
  
   43  | 
  
   0.0257  | 
 
Maximum magnetic field values
at the area of interest (House).
From the measurements performed it can be concluded that the:
·        
	Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.