Starting
Point |
Measurement height
(m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from starting point
(m) |
|||||
3 |
0.5 (above ground
level) |
28.483 |
resultant magnetic field |
51 |
29.053 |
1.0 (above ground
level) |
54.677 |
resultant magnetic field |
51 |
55.771 |
|
1.5 (above ground
level) |
61.120 |
resultant magnetic field |
51 |
62.343 |
|
- |
48.094 |
three-point average exposure level |
|
|
Maximum magnetic field values outside the substation, 0.2 m away from the left
side boundary wall.
Starting Point |
Measurement height
(m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
1 (Kitchen, ground fl.) |
1.0 (above ground
level) |
0.024 |
resultant magnetic field |
37 |
0.0180 |
2 (Bedroom, first fl.) |
1.0 (above
ground level) |
0.030 |
resultant magnetic field |
43 |
0.0257 |
Maximum magnetic field values
at the area of interest (House).
From the measurements performed it can be concluded that the:
·
Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.