   Starting Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Distance
  from starting point (m)  | 
 |||||
| 
   5  | 
  
   0.5
  (above ground level)  | 
  
   0.385  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   0.385  | 
 
| 
   1.0
  (above ground level)  | 
  
   1.996  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   2.036  | 
 |
| 
   1.5
  (above ground level)  | 
  
   1.401  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   1.401  | 
 |
| 
   -  | 
  
   1.261  | 
  
   three-point
  average exposure level  | 
  
   | 
  
   | 
 
Maximum magnetic
field values outside the substation, 0.2 m away from the front
side boundary wall.
| 
   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic
  field level (µT)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public
  (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1
  Back yard (Outdoor)  | 
  
   1.0
  (above ground level)  | 
  
   0.006  | 
  
   resultant
  magnetic field  | 
  
   41  | 
  
   0.0052  | 
 
| 
   2
  Sitting Room  | 
  
   1.0
  (above ground level)  | 
  
   0.002  | 
  
   resultant
  magnetic field  | 
  
   5  | 
  
   0.0001  | 
 
| 
   3 Bedroom 1st Floor  | 
  
   1.0
  (above ground level)  | 
  
   0.005  | 
  
   resultant
  magnetic field  | 
  
   14  | 
  
   0.0013  | 
 
Maximum
magnetic field values at the area of interest (residence).
From the measurements performed it can be concluded that the:
·        
	Magnetic field measurements performed at the area of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.