Starting Point |
Measurement
height (m) |
Magnetic field level (µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance
from starting point (m) |
|||||
5 |
0.5
(above ground level) |
0.385 |
resultant
magnetic field |
50 |
0.385 |
1.0
(above ground level) |
1.996 |
resultant
magnetic field |
51 |
2.036 |
|
1.5
(above ground level) |
1.401 |
resultant
magnetic field |
50 |
1.401 |
|
- |
1.261 |
three-point
average exposure level |
|
|
Maximum magnetic
field values outside the substation, 0.2 m away from the front
side boundary wall.
Starting
Point |
Measurement
height (m) |
Magnetic
field level (µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP General Public
(%) |
Measuring point |
|||||
1
Back yard (Outdoor) |
1.0
(above ground level) |
0.006 |
resultant
magnetic field |
41 |
0.0052 |
2
Sitting Room |
1.0
(above ground level) |
0.002 |
resultant
magnetic field |
5 |
0.0001 |
3 Bedroom 1st Floor |
1.0
(above ground level) |
0.005 |
resultant
magnetic field |
14 |
0.0013 |
Maximum
magnetic field values at the area of interest (residence).
From the measurements performed it can be concluded that the:
·
Magnetic field measurements performed at the area of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.