Miscellaneous - 23A Dodekanisou Street, Lakatamia, Nicosia

Empty Lines

This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:

·         Residence at 23A Dodekanisou Street, Lakatamia 2302, Nicosia on the 03/04/2018 from 10:30 am until 12:00 pm.

The measurements were performed according to the measurements of low-frequency magnetic and electric fields with regard to exposure of human beings (IEC 61786:1998) and measurement procedures with regard to public exposure (IEC 62110:2009). More specifically, three-point measurements were performed to assess the fields (assuming non-uniform fields) in the range of 5 Hz – 32 kHz using the EFA-300 Isotropic Field Analyser. The measurements were performed at the position of interest at three heights 0.5 m, 1.0 m and 1.5 m. above the ground or floor level of the building.

The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respect to the recommended reference levels will ensure respect to the basic restrictions. The reference levels of exposure provided in 1999/519/EC are in accordance to the Cypriot Legislation.

The maximum magnetic and electric field values measured at the location of interest are summarized in the following Table.

Empty LinesEmpty Lines

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP General Public (%)

Measuring point

 

0.5 (above ground level)

0.012

resultant magnetic field

50

0.012

1 (Bedroom 1 outdoor)

1.0 (above ground level)

0.017

resultant magnetic field

50

0.017

 

1.5 (above ground level)

0.058

resultant magnetic field

50

0.058

 

-

0.029

three-point average

50

0.029

Starting Point

Measurement height (m)

Electric field level (V/m)

Field quantity

Frequency (Hz)

ICNIRP General Public (%)

Measuring point

1 (Bedroom 1 outdoor)

1.0 (above ground level)

3.059

resultant magnetic field

50

0.061

Maximum magnetic and electric field values at the location of interest (residence).



From the measurements performed it can be concluded that the:

·         Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.