Starting
Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from starting point (m) |
|||||
1 |
0.5 (above ground level) |
0.157 |
resultant magnetic field |
43 |
0.135 |
1.0 (above ground level) |
0.196 |
resultant magnetic field |
50 |
0.196 |
|
1.5 (above ground level) |
0.107 |
resultant magnetic field |
35 |
0.075 |
|
- |
0.153 |
three-point
average exposure level |
|
|
Maximum magnetic field values outside the substation, 0.2 m away from the left
side boundary wall.
Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public
(%) |
Measuring point |
|||||
4
Bedroom-B, 1st Fl. |
1.0 (above ground
level) |
0.112 |
resultant magnetic field |
20 |
0.0449 |
Maximum magnetic
field values at the
area of interest (house
in close proximity to the substation).
Decision Rule:
·
From the measurements performed it
can be concluded that the magnetic and electric field measurements performed at the position of interest were below the
recommended General Public reference levels of the National Exposure
Limits provided in 1999/519/EC.