   Starting Point  | 
  
   Measurement height
  (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Distance
  from starting point
  (m)  | 
 |||||
| 
   3  | 
  
   0.5 (above ground
  level)  | 
  
   0.587  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.5872  | 
 
| 
   1.0 (above
  ground level)  | 
  
   0.406  | 
  
   resultant magnetic field  | 
  
   58  | 
  
   0.4712  | 
 |
| 
   1.5 (above
  ground level)  | 
  
   0.317  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   0.3232  | 
 |
| 
   -  | 
  
   0.437  | 
  
   three-point average exposure level  | 
  
   | 
  
   | 
 
Maximum magnetic field values outside
the substation, 0.2 m away from the left
side boundary wall.
| 
   Starting Point  | 
  
   Measurement height
  (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1  | 
  
   1.0 (above
  ground level)  | 
  
   0.012  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0010  | 
 
| 
   2  | 
  
   1.0 (above
  ground level)  | 
  
   0.004  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0003  | 
 
| 
   3  | 
  
   1.0 (above
  ground level)  | 
  
   0.003  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0003  | 
 
| 
   4  | 
  
   1.0 (above
  ground level)  | 
  
   0.007  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0006  | 
 
| 
   5  | 
  
   1.0 (above ground
  level)  | 
  
   0.015  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0013  | 
 
| 
   6  | 
  
   1.0 (above
  ground level)  | 
  
   0.015  | 
  
   resultant magnetic field  | 
  
   11  | 
  
   0.0034  | 
 
| 
   7  | 
  
   1.0 (above
  ground level)  | 
  
   0.004  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0003  | 
 
| 
   8  | 
  
   1.0 (above
  ground level)  | 
  
   0.004  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0004  | 
 
| 
   9  | 
  
   1.0 (above
  ground level)  | 
  
   0.004  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0003  | 
 
| 
   10  | 
  
   1.0 (above
  ground level)  | 
  
   0.003  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0003  | 
 
| 
   11  | 
  
   1.0 (above ground
  level)  | 
  
   0.004  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0003  | 
 
| 
   12  | 
  
   1.0 (above
  ground level)  | 
  
   0.003  | 
  
   resultant magnetic field  | 
  
   6  | 
  
   0.0003  | 
 
Maximum magnetic field values at the area of interest (house under construction at Mesa Geitonia area, Limassol).
From the measurements performed it can be concluded that the:
·        
	Point EMF measurements (including uncertainty intervals) were below the recommended general public reference exposure levels to electromagnetic fields of the National Exposure Limits provided in 1999/519/EC.