Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from starting point (m) |
|||||
-2 |
1.0 (above
ground level) |
0.471 |
resultant magnetic field |
51 |
0.480 |
-1 |
1.0 (above
ground level) |
0.473 |
resultant magnetic field |
51 |
0.483 |
0 |
1.0 (above
ground level) |
0.486 |
resultant magnetic field |
51 |
0.496 |
1 |
1.0 (above ground level) |
0.477 |
resultant magnetic field |
51 |
0.487 |
2 |
1.0 (above ground
level) |
0.471 |
resultant magnetic field |
51 |
0.481 |
Starting Point |
Measurement height (m) |
Electric
field level (V/m) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from starting point (m) |
|||||
-2 |
1.0 (above
ground level) |
561.440 |
resultant electric field |
50 |
11.229 |
-1 |
1.0 (above
ground level) |
581.730 |
resultant electric field |
50 |
11.635 |
0 |
1.0 (above
ground level) |
690.370 |
resultant electric field |
51 |
14.084 |
1 |
1.0 (above
ground level) |
615.030 |
resultant electric field |
50 |
12.301 |
2 |
1.0 (above
ground level) |
578.680 |
resultant electric field |
51 |
11.805 |
Maximum magnetic
and electric field values for the investigated overhead power lines (longitudinal profile)
Starting Point |
Measurement height (m) |
Magnetic field level (μΤ) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public
(%) |
Measuring point |
|||||
1 Living
Room (Gr. Floor) |
1.0 (above
ground level) |
0.074 |
resultant magnetic field |
50 |
0.074 |
2 Living
Room (Gr. Floor) |
1.0 (above
ground level) |
0.050 |
resultant magnetic field |
11 |
0.011 |
3 Room (1st Floor) |
1.0 (above ground
level) |
0.083 |
resultant magnetic field |
49 |
0.081 |
4 Room (1st Floor) |
1.0 (above
ground level) |
0.085 |
resultant magnetic field |
50 |
0.085 |
5 Bedroom (1st Floor) |
1.0 (above
ground level) |
0.058 |
resultant magnetic field |
51 |
0.059 |
6 (Outdoors) |
1.0 (above ground level) |
0.113 |
resultant magnetic field |
50 |
0.113 |
7 (Outdoors) |
1.0 (above
ground level) |
0.132 |
resultant magnetic field |
51 |
0.135 |
8 (Outdoors) |
1.0 (above
ground level) |
0.158 |
resultant magnetic field |
51 |
0.161 |
Maximum magnetic field values at the point of interest
(residence at Pyrgos, Limassol).
From the measurements performed it can be concluded that the:
·
Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.