On the 28th of June 2006 at 12:00 pm, magnetic field measurements were performed for Substation 23. The substation of interest is located on the ground floor of the central police department in Limassol.


Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

police.jpg ss280.jpg

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 1: ICNIRP exposure limits for Occupational and General public exposure

The obtained results for the RMS fields inside and outside the substation are shown in tables 2 and 3 respectively and a comparison is made with the ICNIRP recommendations.


Fields inside the substation

Distance from Side (m)

Maximum Magnetic Field (µT) at Z Height (m)
Percentage of ICNIRP Occupational Standard (%)

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Field measurements inside the substation (Distance from left wall inside)

0m from Left Side

14.25

2.85%

8.27

1.65%

2.61

0.52%

0.5m from Left Side

66.11

13.22%

33.78

6.76%

8.34

1.67%

1m from Left Side

480.06

96.01%

512.39

102.48%

13.35

2.67%

1.5m from Left Side

18.48

3.70%

88.06

17.61%

18.08

3.62%

2m from Left Side

105.92

21.18%

83.47

16.69%

27.75

5.55%

2.5m from Left Side

11.58

2.32%

13.71

2.74%

5.17

1.03%

3m from Left Side

18.90

3.78%

25.96

5.19%

17.70

3.54%

Table 2: Maximum field measurements inside substation 23

Fields outside the substation

Distance from side (m)

Maximum Magnetic Field (µT) at Z Height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Substation's front side field measurements

Point A

0.46

0.46%

 

 

 

 

Point B

 

 

0.14

0.14%

 

 

Point C

 

 

 

 

0.07

0.07%

Point D

0.33

0.33%

 

 

 

 

Point E

 

 

0.11

0.11%

 

 

Point F

 

 

 

 

0.05

0.05%

Point G

0.29

0.29%

 

 

 

 

Point H

 

 

0.15

0.15%

 

 

Point I

 

 

 

 

0.05

0.05%

Substation's left side field measurements

Point A

0.04

0.04%

 

 

 

 

Point B

0.07

0.07%

 

 

 

 

Point C

 

 

0.04

0.04%

 

 

Point D

 

 

0.06

0.06%

 

 

Point E

 

 

 

 

0.04

0.04%

Point F

 

 

 

 

0.06

0.06%

Substation's back side field measurements

Point A

0.11

0.11%

 

 

 

 

Point B

 

 

0.14

0.14%

 

 

Point C

 

 

 

 

0.21

0.21%

Point E

0.19

0.19%

 

 

 

 

Point F

 

 

0.23

0.23%

 

 

Point G

 

 

 

 

0.45

0.45%

Point I

0.19

0.19%

 

 

 

 

Point J

 

 

0.21

0.21%

 

 

Point K

 

 

 

 

0.40

0.40%

Substation's back side field measurements at height 2.5m (just below cable tray)

Point D

0.52

0.52%

Point H

3.1

3.1%

Point L

3.18

3.18%

Table 3: Maximum field measurements outside substation 23