High Voltage Overhead Power Lines - 61 Gregori Afxentiou, Limassol

The measurements were performed on the 19th March 2014 at 10:30 a.m. during clear weather conditions. The EMF measurements were performed for the residence “61 Gregori Afxentiou, Pareklisia” which is located in direct proximity to the overhead power line. The following figures provide pictures of the area where EMF measuremets were recorded.

Residence office area 11 kV overhead power line tower


Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 1: ICNIRP exposure limits for Occupational and General public exposure

The maximum obtained magnetic field values are represented below and compared to the ICNIRP specified limits for the General Public. The highest magnetic field value was observed inside the bedroom No.1 at a height of 1 m with a value 0.183 μT and a percentage of 0.183 % as compared to the ICNIRP General Public standard.

The following table summarizes the magnetic field measurements taken in area under investigation.

Magnetic Field Measurements

Distance /m

Maximum Magnetic Field (μT) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

EMF Field Measurements - Line Measurements along the overhead power lines

10m Measurement line

0.075

0.075

0.094

0.094

0.112

0.112

EMF Field Measurements - Line Measurements across the overhead power lines

 10m Measurement line

0.081

0.081

0.098

0.098

0.101

0.101

 Inside residence - Office area
 Measurement point RM-A  --  --  0.047  0.047  --  --
 Insede residence - Bedroom area
 Measurement point RM-C  --  --  0.183  0.183  --  --

Table 2: Magnetic Field Measurements

Also, the maximum obtained electric field values are represented below and compared to the ICNIRP specified limits for the General Public. The highest electric field measurement was observed inside the office area at a height of 1 m. The measured value at this point was 32.84 V/m and a percentage of 0.657% as compared to the ICNIRP General Public standard. It was found that the elevated electric field inside the office area is caused by the house electrical wiring..

The following table summarizes the electric field measurements taken in the area under investigation.

Electric Field Measurements

Distance /m

Maximum Electric Field (V/m) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

EMF Field Measurements - Line Measurements in parallel with the overhead power lines

10m Measurement line

--

--

14.208

0.284

18.814

0.376

EMF Field Measurements - Line Measurements perpendicular to the overhead power lines

10m Measurement line

--

--

21.623

0.432

25.501

0.501

 

EMF Field Measurements - Line Measurements perpendicular to the overhead power lines

 Measurement point RE-A  --  --  32.840 0.657%  --  --
 

EMF Field Measurements - Line Measurements perpendicular to the overhead power lines

 Measurement point RE-D  --  --  1.836  0.037  --  --

Table 3: Electric Field Measurements