High Voltage Overhead Power Lines - Residence 6 Sositheou Street in Agia Fyla, Limassol

The measurements were performed on the 21st of September 2012 at 10:00 am during clear weather conditions. The EMF measurements were performed for the Residence 6 Sositheou Street in Agia Fyla, Limassol which is located in direct proximity to the overhead power line. The following figures provide pictures of the area where EMF measurements were recorded.

Overhead power line tower Residence along overhead power lines


Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.


Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 1: ICNIRP exposure limits for Occupational and General public exposure

The 1st overhead power line Vasilikos1 - Polemidhia1 is of rated voltage of 132 kV and rated maximum nominal power of 150 MVA. At the time when the measurements were performed, the load of the overhead power line was 38.43 MVA. The Resultant Load of all three phases for the Vasilikos1 - Polemidhia1 was 25.62 % utilisation of the nominal load power.

The 2nd overhead power line Vasilikos2 - Polemidhia2 is of rated voltage of 132 kV and rated maximum nominal power of 150 MVA. At the time when the measurements were performed, the load of the overhead power line was 38.35 MVA. The Resultant Load of all three phases for the Vasilikos2 - Polemidhia2 was 25.57 % utilisation of the nominal load power.

The highest magnetic field measurement was observed along the overhead power lines, with a value 0.302 μT (3 m away from the starting point, at 1.75 m height) and a percent- age of 0.302 % as compared to the ICNIRP General Public standard. Accordingly a detailed description of the maximum measured magnetic elds in the area under investigation is shown in the table below.

The following table summarizes the magnetic field measurements taken in the area under investigation.

Magnetic Field Measurements

Distance /m

Maximum Magnetic Field (μT) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

EMF Field Measurements - Line Measurements along the overhead power lines

10m Measurement line

0.243

0.243

0.267

0.267

0.302

0.302

EMF Field Measurements - Line Measurements across the overhead power lines

 17m Measurement line

0.254

0.254

0.273

0.273

0.296

0.296

Inside the residence kitchen

 Measurement Point M-A

--

--

0.258

0.258 

--

--

Table 2: Magnetic Field Measurements

The highest electric field measurement was observed across the overhead power lines, with a value 100.38 V/m (17 m away from the starting point, at 1m height) and a percentage of 2.008 % as compared to the ICNIRP General Public standard.

The following table summarizes the electric field measurements taken in the area under investigation.

Electric Field Measurements

Distance /m

Maximum Electric Field (V/m) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

EMF Field Measurements - Inside the residence kitchen

Measurement Point E-A

--

--

8.050

0.161

--

--

EMF Field Measurements - Line Measurements along the overhead power lines

10m Measurement line

--

--

25.127

0.503

82.267

1.645

EMF Field Measurements - Line Measurements along the overhead power lines

 17m Measurement line

--

--

100.380

2.008

99.591

1.992

Table 3: Electric Field Measurements