The measurements were performed on the 21st of September 2012 at 10:00 am during clear weather conditions. The EMF measurements were performed for the Residence 6 Sositheou Street in Agia Fyla, Limassol which is located in direct proximity to the overhead power line. The following figures provide pictures of the area where EMF measurements were recorded.
Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.
Reference levels for Occupational exposure ICNIRP |
|||
Frequency |
Electric Field Strength, E (V/m) |
Magnetic Field Strength, H (A/m) |
Magnetic Flux Density, B (µT) |
50 Hz |
10000 |
400 |
500 |
Reference levels for General Public exposure ICNIRP |
|||
Frequency |
Electric Field Strength, E (V/m) |
Magnetic Field Strength, H (A/m) |
Magnetic Flux Density, B (µT) |
50 Hz |
5000 |
80 |
100 |
Table 1: ICNIRP exposure limits for Occupational and General public exposure
The 1st overhead power line Vasilikos1 - Polemidhia1 is of rated voltage of 132 kV and rated maximum nominal power of 150 MVA. At the time when the measurements were performed, the load of the overhead power line was 38.43 MVA. The Resultant Load of all three phases for the Vasilikos1 - Polemidhia1 was 25.62 % utilisation of the nominal load power.
The 2nd overhead power line Vasilikos2 - Polemidhia2 is of rated voltage of 132 kV and rated maximum nominal power of 150 MVA. At the time when the measurements were performed, the load of the overhead power line was 38.35 MVA. The Resultant Load of all three phases for the Vasilikos2 - Polemidhia2 was 25.57 % utilisation of the nominal load power.
The highest magnetic field measurement was observed along the overhead power lines, with a value 0.302 μT (3 m away from the starting point, at 1.75 m height) and a percent- age of 0.302 % as compared to the ICNIRP General Public standard. Accordingly a detailed description of the maximum measured magnetic elds in the area under investigation is shown in the table below.
The following table summarizes the magnetic field measurements taken in the area under investigation.
Magnetic Field Measurements |
||||||
Distance /m |
Maximum Magnetic Field (μT) at Z Height /m - Percentage of ICNIRP General Public Standard /% |
|||||
0.3m |
ICNIRP % |
1m |
ICNIRP % |
1.75m |
ICNIRP % |
|
EMF Field Measurements - Line Measurements along the overhead power lines |
||||||
10m Measurement line |
0.243 |
0.243 |
0.267 |
0.267 |
0.302 |
0.302 |
EMF Field Measurements - Line Measurements across the overhead power lines |
||||||
17m Measurement line |
0.254 |
0.254 |
0.273 |
0.273 |
0.296 |
0.296 |
Inside the residence kitchen |
||||||
Measurement Point M-A |
-- |
-- |
0.258 |
0.258 |
-- |
-- |
Table 2: Magnetic Field Measurements
The highest electric field measurement was observed across the overhead power lines, with a value 100.38 V/m (17 m away from the starting point, at 1m height) and a percentage of 2.008 % as compared to the ICNIRP General Public standard.
The following table summarizes the electric field measurements taken in the area under investigation.
Electric Field Measurements |
||||||
Distance /m |
Maximum Electric Field (V/m) at Z Height /m - Percentage of ICNIRP General Public Standard /% |
|||||
0.3m |
ICNIRP % |
1m |
ICNIRP % |
1.75m |
ICNIRP % |
|
EMF Field Measurements - Inside the residence kitchen |
||||||
Measurement Point E-A |
-- |
-- |
8.050 |
0.161 |
-- |
-- |
EMF Field Measurements - Line Measurements along the overhead power lines |
||||||
10m Measurement line |
-- |
-- |
25.127 |
0.503 |
82.267 |
1.645 |
EMF Field Measurements - Line Measurements along the overhead power lines |
||||||
17m Measurement line |
-- |
-- |
100.380 |
2.008 |
99.591 |
1.992 |
Table 3: Electric Field Measurements