High Voltage Overhead Power Lines - Nicosia/Limassol old road, Limassol

The measurements were performed for the plot area near the Overhead Power Lines at 10:00 am during cloudy weather conditions. The EMF measurements were performed for the residence "Nicosia-Limassol old road, Mossfiloti" which is located in direct proximity to the overhead power line. The following gures provide pictures of the area where EMF measuremets were recorded.

Overhead power line tower Residence along overhead power lines


Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.


Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 1: ICNIRP exposure limits for Occupational and General public exposure

The 1st overhead power line Alambra-Vasilikos No. 1 is of rated voltage of 132 kV and rated maximum nominal power of 145 MVA. At the time when the measurements were performed, the load of the overhead power line was 19.3 MVA. The Resultant Load of all three phases for the Alambra-Vasilikos No. 1 was 13.31 % utilisation of the nominal load power.

The 2nd overhead power line Alambra-Vasilikos No. 2 is of rated voltage of 132 kV and rated maximum nominal power of 145 MVA. At the time when the measurements were performed, the load of the overhead power line was 19.6 MVA. The Resultant Load of all three phases for the Alambra-Vasilikos No. 2 was 13.52 % utilisation of the nominal load power.

The highest magnetic field measurement was observed along the overhead power lines, with a value 0.370 μT (0 m away from the starting point, at 1.75 m height) and a percentage of 0.370 % as compared to the ICNIRP General Public standard. Accordingly a detailed description of the maximum measured magnetic fields in the area under investigation is shown in the table below.

The following table summarizes the magnetic field measurements taken in the area under investigation.

Magnetic Field Measurements

Distance /m

Maximum Magnetic Field (μT) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

EMF Field Measurements - Line Measurements along the overhead power lines

40m Measurement line

0.318

0.318

0.342

0.342

0.370

0.370

EMF Field Measurements - Line Measurements across the overhead power lines

 50m Measurement line

0.265

0.265

0.284

0.284

0.302

0.302

Table 2: Magnetic Field Measurements

The highest electric field measurement was observed along the overhead power lines, with a value 294.70 V/m (6 m away from the starting point, at 1m height) and a percentage of 5.894 % as compared to the ICNIRP General Public standard.

The following table summarizes the electric field measurements taken in the area under investigation.

Electric Field Measurements

Distance /m

Maximum Electric Field (V/m) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

EMF Field Measurements - Line Measurements along the overhead power lines

40m Measurement line

--

--

294.700

5.894

283.250

5.665

EMF Field Measurements - Line Measurements along the overhead power lines

 50m Measurement line

--

--

144.450

2.889

138.240

2.765

Table 3: Electric Field Measurements