Starting
Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP
General Public (%) |
Distance
from starting point (m) |
|||||
0 |
0.5 (above ground
level) |
0.213 |
resultant magnetic field |
40 |
0.170 |
|
1.0 (above ground
level) |
0.175 |
resultant magnetic field |
51 |
0.179 |
|
1.5 (above ground
level) |
0.079 |
resultant magnetic field |
50 |
0.079 |
|
- |
0.156 |
three-point average exposure
level |
|
0.143 |
Starting
Point |
Measurement height (m) |
Electric field level (V/m) |
Field quantity |
Frequency (Hz) |
ICNIRP
General Public (%) |
Distance
from starting point (m) |
|||||
3 (longitudinal) |
1.0 (above ground
level) |
286.371 |
Resultant electric field |
51 |
5.842 |
Maximum magnetic and electric field values for the investigated
overhead power lines.
Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
3 |
0.5
(above ground level) |
0.002 |
resultant magnetic field |
9 |
0.0004 |
(outside
field) |
1.0
(above ground level) |
0.003 |
resultant magnetic field |
10 |
0.0005 |
|
1.5
(above ground level) |
0.006 |
resultant magnetic field |
11 |
0.0013 |
|
- |
0.004 |
three-point average exposure level |
- |
0.0007 |
Maximum magnetic field values at the point of interest
(field).
From the measurements performed it can be concluded that the:
·
Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.