Underground Power Cables - 3 Chrysostomou Smyrnhs Street

On the 10th of April 2008 at 10:00 am electric and magnetic field measurements were performed for residence 3 Chrysostomou Smyrnhs Street in Larnaca. The measured residence is located in close proximity to 11 kV underground power cables which pass through the area.

During the period that the EMF measurements were taken the underground cable was not yet connected to the electric grid. Due to this fact, the underground cable does not contribute to the electromagnetic profile of the area.

The configuration and installation of the underground power cable are represented in the following figures.

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 1: ICNIRP Exposure limits for Occupational and General Public exposure

A detailed description of the maximum measured magnetic fields inside and outside the residence is shown in the following tables. A comparison is also made with the ICNIRP recommendations.

3 Chrysostomou Smyrnhs street Residence Magnetic Field Measurements- Inside Area

Measurement Point

Maximum Magnetic Field / µT at Z Height /m -

Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1 m

ICNIRP %

2 m

ICNIRP %

Inside Residence - Bedroom

Measurement Point A

----

----

0.009

0.009%

----

----

Measurement Point B

----

----

0.016

0.016%

----

----

Measurement Point C

----

----

----

----

0.25

0.25%

Measurement Point D

0.445

0.445%

----

----

----

----

Measurement Point E

----

----

----

----

4.0

4.0%

Table 2: Maximum Magnetic Field measurements inside the Residence - Bedroom

3 Chrysostomou Smyrnhs street Residence Magnetic Field Measurements- Outside Area

Measurement Point

Maximum Magnetic Field / µT at Z Height /m -

Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1 m

ICNIRP %

1.75 m

ICNIRP %

Measurement along the underground cable

0m away from starting point

0.008

0.010%

0.010

0.010%

0.012

0.012%

1m away from starting point

0.014

0.019%

0.019

0.019%

0.023

0.023%

2m away from starting point

0.015

0.019%

0.019

0.019%

0.022

0.022%

3m away from starting point

0.015

0.019%

0.019

0.019%

0.022

0.022%

4m away from starting point

0.015

0.020%

0.020

0.020%

0.024

0.024%

5m away from starting point

0.015

0.019%

0.019

0.019%

0.023

0.023%

Measurement across the underground cable

0m away from starting point

0.048

0.048%

0.058

0.058%

0.069

0.069%

1m away from starting point

0.053

0.053%

0.066

0.066%

0.079

0.079%

2m away from starting point

0.055

0.055%

0.073

0.073%

0.087

0.087%

3m away from starting point

0.032

0.032%

0.024

0.024%

0.030

0.030%

4m away from starting point

0.020

0.020%

0.025

0.025%

0.033

0.033%

5m away from starting point

0.024

0.024%

0.029

0.029%

0.037

0.037%

6m away from starting point

0.021

0.021%

0.028

0.028%

0.033

0.033%

7m away from starting point

0.017

0.017%

0.021

0.021%

0.024

0.024%

8m away from starting point

0.013

0.013%

0.016

0.016%

0.018

0.018%

9m away from starting point

0.012

0.012%

0.014

0.014%

0.016

0.016%

Table 3: Maximum Magnetic Field measurements outside the Residence-Underground Cable Area