   Measurement height (m)  | 
  
  
   Magnetic field level (µT)  | 
  
  
   Field quantity  | 
  
  
   Frequency (Hz)  | 
  
  
   ICNIRP General Public (%)  | 
  
 |
| 
   Distance from starting point (m)  | 
  
 |||||
| 
   | 
  
  
   0.5 (above ground level)  | 
  
  
   0.284  | 
  
  
   resultant magnetic field  | 
  
  
   51  | 
  
  
   0.290  | 
  
 
| 
   1  | 
  
  
   1.0 (above ground level)  | 
  
  
   0.468  | 
  
  
   resultant magnetic field  | 
  
  
   51  | 
  
  
   0.477  | 
  
 
| 
   | 
  
  
   1.5 (above ground level)  | 
  
  
   0.377  | 
  
  
   resultant magnetic field  | 
  
  
   51  | 
  
  
   0.385  | 
  
 
| 
   | 
  
  
   -  | 
  
  
   0.376  | 
  
  
   three-point average  | 
  
  
   | 
  
  
   0.384  | 
  
 
Maximum
magnetic field values outside the substation, 0.2
m away from the right side boundary wall.
| 
   Starting Point  | 
  
  
   Measurement height (m)  | 
  
  
   Magnetic field level (µT)  | 
  
  
   Field quantity  | 
  
  
   Frequency (Hz)  | 
  
  
   ICNIRP General Public (%)  | 
  
 
| 
   Measuring point  | 
  
 |||||
| 
   3 (Outside -Swimming Pool)  | 
  
  
   0.5 (above ground level)  | 
  
  
   0.003  | 
  
  
   resultant magnetic field  | 
  
  
   18  | 
  
  
   0.001  | 
  
 
| 
   | 
  
  
   1.0 (above ground level)  | 
  
  
   0.002  | 
  
  
   resultant magnetic field  | 
  
  
   11  | 
  
  
   0.000  | 
  
 
| 
   1.5 (above ground level)  | 
  
  
   0.007  | 
  
  
   resultant magnetic field  | 
  
  
   29  | 
  
  
   0.004  | 
  
 |
| 
   -  | 
  
  
   0.004  | 
  
  
   three-point average  | 
  
  
   | 
  
  
   0.001  | 
  
 
Maximum magnetic field values at the location of
interest (residence).
From the measurements performed it can be concluded that the:
·        
	Magnetic field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.