Substation - Substation Polymnia, Filellinon Street

The measured substation/apartment is located in the 13, Filellinon str. in Paralimni. The measurements were performed on the 1st of July 2008 at 9:30 am. Substation POLYMNIA is situated in the car park of the Polymnia Court.

The substation is rated at a nominal power of 200 KVA. At the time when the measurements were performed, the substation load power was recorded as:


Red Phase

Yellow Phase

Blue Phase

139A

77A

85A

Table 1: Measured load current


The resultant load of all three phases was 36.1% utilization of the nominal load current.

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organizations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 2: ICNIRP Exposure limits for Occupational and General Public exposure

A detailed description of the maximum measured magnetic fields in the outside area is shown in the following table.

Outside Field Measurements

Distance from Side /m

Maximum Magnetic Field (µT) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

Substation Front Side

0m

0.568

0.57%

0.531

0.53%

0.472

0.47%

1m

0.172

0.17%

0.152

0.15%

0.138

0.14%

2m

0.054

0.05%

0.055

0.06%

0.052

0.05%

Substation Right Side

0m

4.002

4.00%

5.058

5.06%

2.972

2.97%

1m

0.307

0.31%

0.318

0.32%

0.242

0.24%

2m

0.049

0.05%

0.049

0.05%

0.048

0.05%

Substation Back Side

0m

0.036

0.04%

0.069

0.07%

0.088

0.09%

1m

0.019

0.02%

0.026

0.03%

0.027

0.03%

2m

0.014

0.01%

0.014

0.01%

0.012

0.01%

Substation Left Side

0m

0.066

0.07%

0.066

0.07%

0.066

0.07%

1m

0.021

0.02%

0.022

0.02%

0.019

0.02%

2m

0.016

0.02%

0.016

0.02%

0.015

0.02%

Table 3: Magnetic Field Measurements in the outside area - Polymnia Substation

Accordingly a detailed description of the maximum measured magnetic fields in the inside area is shown in the table below.

Mesh Field Measurements inside Polymnia Substation

Distance from Side /m

Maximum Magnetic Field (µT) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

Field Measurements inside the Substation

0m

8.786

1.76%

10.732

2.15%

9.933

1.99%

0.5m

2.528

0.51%

1.282

0.26%

0.927

0.19%

1m

2.639

0.53%

1.429

0.29%

1.694

0.34%

1.5m

3.37

0.67%

1.486

0.30%

0.87

0.17%

2m

8.614

1.72%

2.953

0.59%

2.219

0.44%

2.5m

34.868

6.97%

30.682

6.14%

10.984

2.20%

3m

5.209

1.04%

9.305

1.86%

9.305

1.86%

3.5m

2.084

0.42%

3.484

0.70%

1.995

0.40%

4m

0.789

0.16%

0.87

0.17%

0.687

0.14%

Table 4: Magnetic Field Measurements inside Polymnia Substation

Field Measurements Inside Polymnia Court Apartment

Measurement Point

Maximum Magnetic Field (µT) at Z Height /m - Percentage of ICNIRP General Public Standard /%

0.3m

ICNIRP %

1m

ICNIRP %

1.75m

ICNIRP %

Inside Polymnia Court Apartment

Measurement Point A

--

--

0.008

0.018%

--

--

Measurement Point B

--

--

0.011

0.011%

--

--

Measurement Point C

--

--

0.012

0.012%

--

--

Table 5: Magnetic Field Measurements inside the Polymnia Court Apartment