Substation - 16 Ektoros Street, Aradippou

Empty Lines

This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:

·         Substation PYTHAGORAS STREET and residence at 16 Ektoros Street Aradippou on the 13/03/2019 from 11:00 am until 12:00 pm.

The measurements were performed according to the measurements of low-frequency magnetic and electric fields with regard to exposure of human beings (IEC 61786:1998) and measurement procedures with regard to public exposure (IEC 62110:2009). More specifically, three-point measurements were performed to assess the fields (assuming non-uniform fields) in the range of 5 Hz – 32 kHz using the EFA- 300 Isotropic Field Analyser. The measurements were performed at the position of interest at three heights 0.5 m, 1.0 m and 1.5 m. above the ground or floor level of the building. Beside power equipment or in a building, measurement was performed at a horizontal distance of 0.2 m and 2.0 m from its surface or boundary wall. It is important to note that in this investigation additional point measurements were taken at locations indicated by the customer (non-standardized measurements outside the measurement procedures with regard to public exposure (IEC 62110:2009).

The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respect to the recommended reference levels will ensure respect to the basic restrictions. The reference levels of exposure provided in 1999/519/EC are in accordance to the Cypriot Legislation.

The maximum magnetic field values measured at the location of interest are summarized in the following Tables.

Empty LinesEmpty LinesEmpty LinesEmpty LinesEmpty LinesEmpty Lines

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from

starting point (m)

 

 

0

0.5 (above ground level)

0.164

resultant magnetic field

50

0.164

1.0 (above ground level)

0.703

resultant magnetic field

50

0.703

1.5 (above ground level)

0.633

resultant magnetic field

51

0.646

-

0.500

three-point average

 

0.500

Maximum magnetic field values outside the substation, 0.2 m away from the front side boundary wall.

 

 

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Measuring point

1 (Outdoors)

Drive way directly above the incoming substation cables

0.5 (above ground level)

0.028

resultant magnetic field

37

0.021

1.0 (above ground level)

0.029

resultant magnetic field

31

0.018

1.5 (above ground level)

0.015

resultant magnetic field

21

0.006

-

0.024

three-point average

 

0.024

Maximum magnetic field values at the location of interest (residence).



From the measurements performed it can be concluded that the:

·         Magnetic field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.