   Measurement height (m)  | 
  
  
   Magnetic field level (µT)  | 
  
  
   Field quantity  | 
  
  
   Frequency (Hz)  | 
  
  
   ICNIRP
  General Public (%)  | 
  
 |
| 
   Distance from starting point (m)  | 
  
 |||||
| 
   0  | 
  
  
   0.5
  (above ground level)  | 
  
  
   0.033  | 
  
  
   resultant
  magnetic field  | 
  
  
   51  | 
  
  
   0.034  | 
  
 
| 
   | 
  
  
   1.0
  (above ground level)  | 
  
  
   0.187  | 
  
  
   resultant
  magnetic field  | 
  
  
   51  | 
  
  
   0.191  | 
  
 
| 
   | 
  
  
   1.5
  (above ground level)  | 
  
  
   0.375  | 
  
  
   resultant
  magnetic field  | 
  
  
   51  | 
  
  
   0.382  | 
  
 
| 
   | 
  
  
   -  | 
  
  
   0.198  | 
  
  
   three-point average exposure level  | 
  
  
   | 
  
  
   | 
  
 
Maximum magnetic
field values at the pole transformer.
| 
   Starting Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic
  field level (µT)  | 
  
   Field
  quantity  | 
  
   Frequency
  (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1 (Outdoors)  | 
  
   1.0
  (above ground level)  | 
  
   0.002  | 
  
   resultant
  magnetic field  | 
  
   7  | 
  
   0.0003  | 
 
| 
   2 (Outdoors)  | 
  
   1.0
  (above ground level)  | 
  
   0.005  | 
  
   resultant
  magnetic field  | 
  
   7  | 
  
   0.0006  | 
 
| 
   3 (Outdoors)  | 
  
   1.0
  (above ground level)  | 
  
   0.022  | 
  
   resultant
  magnetic field  | 
  
   9  | 
  
   0.0040  | 
 
Maximum magnetic field values
at the area of interest (residence).
From the measurements performed it can be concluded that the:
·        
	Magnetic field measurements performed at the area of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC [3].