Pole Mounted Transformer - 10B Avlidos Street, Leivadia

The measurements were performed on the 10th of December 2008 at 09:00 am. The EMF measurements were performed inside and outside the residence and in direct proximity to the pole mounted transformer.

The pole mounted transformer is rated at a nominal power of 100 KVA. At the time when the measurements were performed, the transformer load power was recorded as:


Red Phase

Yellow Phase

Blue Phase

2 A

5 A

10 A

Table 1: ICNIRP Exposure limits for Occupational and General Public exposure


The Resultant Load of all three phases was 4% utilisation of the nominal load current.

 

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

 

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength, E (V/m)

Magnetic Field Strength, H (A/m)

Magnetic Flux Density, B (µT)

50 Hz

5000

80

100

Table 2: ICNIRP Exposure limits for Occupational and General Public exposure

 

The highest magnetic field inside the residence was observed in the master bedroom, behind the television, with a value 4.34 µT and a percentage of 4.34% as compared to the ICNIRP General Public standard. Accordingly the highest magnetic field value outside the residence was observed in front of the pole mounted transformer, with value 0.0594 µT and a percentage of 0.0594% as compared to the ICNIRP General Public standard.

A detailed description of the maximum measured magnetic fields inside and outside the residence is shown in the following tables. A comparison is also made with the ICNIRP recommendations.

Substation Field Measurements

Distance from Side /m

Maximum Magnetic Field at Z Height /m - Percentage of ICNIRP General Public Standard /%

Magnetic Field  /µT

ICNIRP %

Bedroom A

0.12

0.12%

Master Bedroom (TV)

4.34

4.34%

Bedroom B

0.30

0.30%

Table 3: Magnetic Field Measurements inside the residence

Substation Field Measurements

Distance from Side /m

Maximum Magnetic Field at Z Height /m - Percentage of ICNIRP General Public Standard /%

Magnetic Field  /µT

ICNIRP %

In front of Pole mounted transformer

0.594

0.0594%

Behind Pole mounted transformer

0.0356 

0.0356%

Parking area

0.0290

0.0290%

Table 4: Magnetic Field Measurements outside the residence