Overhead Power Lines - Mosfiloti, Larnaca

Empty Lines

This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:

·         Overhead Power Lines Vasiliko-Alambra & Kofinou-Alambra in direct proximity to the investigated area, residence at 11 Lemesou Avenue, Mosfiloti 7647, Larnaca, on the 03/11/2021 from 09:00 am until 10:30 am.

The measurements were performed according to the measurements of low-frequency magnetic fields with regard to exposure of human beings (IEC 61786:1998) and measurement procedures with regard to public exposure (IEC 62110:2009). More specifically, the largest magnetic field level is found under conductors at the point on the span where the conductors are closest to the ground. Therefore, the position where the field level is the maximum was found by first measuring at 1.0 m above the ground along the path parallel to the overhead line under conductors where possible at appropriate intervals (longitudinal profile), in the range of 5 Hz – 32 kHz using the EFA-300 Isotropic Field Analyser. Then, in order to discover whether anoter peak occurs, measurements were performed at 1.0 m above the ground along the path perpendicular to the overhead line, at the point of the longitudinal profile maximum (lateral profile).

In addition, three-point measurements were performed to assess the fields at the position of interest (assuming non-uniform fields). The measurements were performed at the position of interest at three heights 0.5 m, 1.0 m and 1.5 m. above the ground or floor level of the building. It is important to note that in this investigation additional point measurements were taken at locations indicated by the customer (non- standardized measurements outside the measurement procedures with regard to public exposure (IEC 62110:2009).

The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respect to the recommended reference levels will ensure respect to the basic restrictions. The reference levels of exposure provided in 1999/519/EC are in accordance to the Cypriot Legislation.

The maximum magnetic field values measured along the longitudinal and lateral profiles of the overhead power lines and at the location of interest are summarized in the following Tables.

Empty LinesEmpty LinesEmpty LinesEmpty LinesEmpty LinesEmpty Lines

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from starting point (m)

0

1.0 (above ground level)

1.804

resultant magnetic field

51

1.840

1

1.0 (above ground level)

1.756

resultant magnetic field

50

1.756

2

1.0 (above ground level)

1.676

resultant magnetic field

51

1.709

3

1.0 (above ground level)

1.578

resultant magnetic field

50

1.578

4

1.0 (above ground level)

1.396

resultant magnetic field

50

1.396

Starting Point

Measurement height (m)

Electric field level (V/m)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from starting point (m)

0

1.0 (above ground level)

1550.000

resultant magnetic field

51

31.620

1

1.0 (above ground level)

1287.400

resultant magnetic field

50

25.748

2

1.0 (above ground level)

1009.900

resultant magnetic field

51

20.602

3

1.0 (above ground level)

640.370

resultant magnetic field

50

12.807

4

1.0 (above ground level)

179.160

resultant magnetic field

50

3.583

Maximum magnetic and electric field values for the investigated overhead power lines.

 

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Measuring point

1. Washing Area

(Rooftop)

1.0 (above ground level)

1.752

resultant magnetic field

51

1.787

2. Heater Engine Room (Rooftop)

1.0 (above ground level)

1.671

resultant magnetic field

50

1.671

3. Cooking Area

1.0 (above ground level)

1.168

resultant magnetic field

51

1.191

4. TV Room

1.0 (above ground level)

1.149

resultant magnetic field

51

1.172

5. Veranda (Outdoors)

1.0 (above ground level)

1.241

resultant magnetic field

51

1.265

6. Sitting Room

1.0 (above ground level)

1.134

resultant magnetic field

50

1.134

7. Bedroom

1.0 (above ground level)

1.108

resultant magnetic field

50

1.108

8. Kitchen

1.0 (above ground level)

0.996

resultant magnetic field

51

1.016

9. W.C

1.0 (above ground level)

0.825

resultant magnetic field

51

0.841

10. W.C

1.0 (above ground level)

0.877

resultant magnetic field

50

0.877

11. Bedroom

1.0 (above ground level)

0.841

resultant magnetic field

51

0.858

12. Bedroom

1.0 (above ground level)

0.966

resultant magnetic field

51

0.985

13. Veranda (Outdoors)

1.0 (above ground level)

0.953

resultant magnetic field

51

0.972

14. Veranda (Outdoors)

1.0 (above ground level)

0.764

resultant magnetic field

51

0.779

15. Stairs (Outdoors)

1.0 (above ground level)

0.657

resultant magnetic field

50

0.657

Maximum magnetic field values at the point of interest (residence on first floor).

From the measurements performed it can be concluded that the:

·         Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.