   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Distance from
  starting point (m)  | 
 |||||
| 
   0  | 
  
   1.0 (above ground level)  | 
  
   1.804  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   1.840  | 
 
| 
   1  | 
  
   1.0 (above
  ground level)  | 
  
   1.756  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   1.756  | 
 
| 
   2  | 
  
   1.0 (above
  ground level)  | 
  
   1.676  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   1.709  | 
 
| 
   3  | 
  
   1.0 (above
  ground level)  | 
  
   1.578  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   1.578  | 
 
| 
   4  | 
  
   1.0 (above ground level)  | 
  
   1.396  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   1.396  | 
 
| 
   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Electric field
  level (V/m)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Distance from
  starting point (m)  | 
 |||||
| 
   0  | 
  
   1.0 (above
  ground level)  | 
  
   1550.000  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   31.620  | 
 
| 
   1  | 
  
   1.0 (above
  ground level)  | 
  
   1287.400  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   25.748  | 
 
| 
   2  | 
  
   1.0 (above
  ground level)  | 
  
   1009.900  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   20.602  | 
 
| 
   3  | 
  
   1.0 (above
  ground level)  | 
  
   640.370  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   12.807  | 
 
| 
   4  | 
  
   1.0 (above
  ground level)  | 
  
   179.160  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   3.583  | 
 
Maximum
magnetic and electric field values for the investigated overhead power lines.
| 
   Starting Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic field level (µT)  | 
  
   Field quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1. Washing Area (Rooftop)  | 
  
   1.0 (above ground level)  | 
  
   1.752  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   1.787  | 
 
| 
   2. Heater Engine Room (Rooftop)  | 
  
   1.0 (above
  ground level)  | 
  
   1.671  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   1.671  | 
 
| 
   3. Cooking Area  | 
  
   1.0 (above
  ground level)  | 
  
   1.168  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   1.191  | 
 
| 
   4. TV Room  | 
  
   1.0 (above ground level)  | 
  
   1.149  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   1.172  | 
 
| 
   5. Veranda
  (Outdoors)  | 
  
   1.0 (above
  ground level)  | 
  
   1.241  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   1.265  | 
 
| 
   6. Sitting Room  | 
  
   1.0 (above ground level)  | 
  
   1.134  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   1.134  | 
 
| 
   7. Bedroom  | 
  
   1.0 (above
  ground level)  | 
  
   1.108  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   1.108  | 
 
| 
   8. Kitchen  | 
  
   1.0 (above
  ground level)  | 
  
   0.996  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   1.016  | 
 
| 
   9. W.C  | 
  
   1.0 (above ground level)  | 
  
   0.825  | 
  
   resultant magnetic field  | 
  
   51  | 
  
   0.841  | 
 
| 
   10. W.C  | 
  
   1.0 (above
  ground level)  | 
  
   0.877  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   0.877  | 
 
| 
   11. Bedroom  | 
  
   1.0 (above
  ground level)  | 
  
   0.841  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   0.858  | 
 
| 
   12. Bedroom  | 
  
   1.0 (above
  ground level)  | 
  
   0.966  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   0.985  | 
 
| 
   13. Veranda
  (Outdoors)  | 
  
   1.0 (above
  ground level)  | 
  
   0.953  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   0.972  | 
 
| 
   14. Veranda
  (Outdoors)  | 
  
   1.0 (above
  ground level)  | 
  
   0.764  | 
  
   resultant
  magnetic field  | 
  
   51  | 
  
   0.779  | 
 
| 
   15. Stairs (Outdoors)  | 
  
   1.0 (above ground level)  | 
  
   0.657  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.657  | 
 
Maximum magnetic field values at the point of
interest (residence on first floor).
From the measurements performed it can be concluded that the:
·        
	Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.