Starting
Point |
Measurement
height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from
starting point (m) |
|||||
0 |
1.0 (above ground level) |
1.804 |
resultant magnetic field |
51 |
1.840 |
1 |
1.0 (above
ground level) |
1.756 |
resultant
magnetic field |
50 |
1.756 |
2 |
1.0 (above
ground level) |
1.676 |
resultant
magnetic field |
51 |
1.709 |
3 |
1.0 (above
ground level) |
1.578 |
resultant
magnetic field |
50 |
1.578 |
4 |
1.0 (above ground level) |
1.396 |
resultant magnetic field |
50 |
1.396 |
Starting
Point |
Measurement
height (m) |
Electric field
level (V/m) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance from
starting point (m) |
|||||
0 |
1.0 (above
ground level) |
1550.000 |
resultant
magnetic field |
51 |
31.620 |
1 |
1.0 (above
ground level) |
1287.400 |
resultant
magnetic field |
50 |
25.748 |
2 |
1.0 (above
ground level) |
1009.900 |
resultant
magnetic field |
51 |
20.602 |
3 |
1.0 (above
ground level) |
640.370 |
resultant
magnetic field |
50 |
12.807 |
4 |
1.0 (above
ground level) |
179.160 |
resultant
magnetic field |
50 |
3.583 |
Maximum
magnetic and electric field values for the investigated overhead power lines.
Starting Point |
Measurement
height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
1. Washing Area (Rooftop) |
1.0 (above ground level) |
1.752 |
resultant magnetic field |
51 |
1.787 |
2. Heater Engine Room (Rooftop) |
1.0 (above
ground level) |
1.671 |
resultant
magnetic field |
50 |
1.671 |
3. Cooking Area |
1.0 (above
ground level) |
1.168 |
resultant
magnetic field |
51 |
1.191 |
4. TV Room |
1.0 (above ground level) |
1.149 |
resultant magnetic field |
51 |
1.172 |
5. Veranda
(Outdoors) |
1.0 (above
ground level) |
1.241 |
resultant
magnetic field |
51 |
1.265 |
6. Sitting Room |
1.0 (above ground level) |
1.134 |
resultant magnetic field |
50 |
1.134 |
7. Bedroom |
1.0 (above
ground level) |
1.108 |
resultant
magnetic field |
50 |
1.108 |
8. Kitchen |
1.0 (above
ground level) |
0.996 |
resultant
magnetic field |
51 |
1.016 |
9. W.C |
1.0 (above ground level) |
0.825 |
resultant magnetic field |
51 |
0.841 |
10. W.C |
1.0 (above
ground level) |
0.877 |
resultant
magnetic field |
50 |
0.877 |
11. Bedroom |
1.0 (above
ground level) |
0.841 |
resultant
magnetic field |
51 |
0.858 |
12. Bedroom |
1.0 (above
ground level) |
0.966 |
resultant
magnetic field |
51 |
0.985 |
13. Veranda
(Outdoors) |
1.0 (above
ground level) |
0.953 |
resultant
magnetic field |
51 |
0.972 |
14. Veranda
(Outdoors) |
1.0 (above
ground level) |
0.764 |
resultant
magnetic field |
51 |
0.779 |
15. Stairs (Outdoors) |
1.0 (above ground level) |
0.657 |
resultant magnetic field |
50 |
0.657 |
Maximum magnetic field values at the point of
interest (residence on first floor).
From the measurements performed it can be concluded that the:
·
Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.