Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Field
quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Distance
from starting
point (m) |
|||||
2 |
1.0 (above ground level) |
1.015 |
resultant
magnetic field |
50 |
1.015 |
1 |
1.0 (above ground level) |
1.095 |
resultant
magnetic field |
51 |
1.117 |
0 |
1.0 (above ground level) |
1.142 |
resultant
magnetic field |
51 |
1.165 |
-1 |
1.0 (above ground level) |
1.123 |
resultant
magnetic field |
51 |
1.145 |
-2 |
1.0 (above ground level) |
1.057 |
resultant
magnetic field |
51 |
1.078 |
Maximum magnetic field values for the investigated
overhead power lines (lateral profile).
Starting
Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
Measuring point |
|||||
2 Bedroom-1 |
0.5 (above ground level) |
0.035 |
resultant magnetic field |
44 |
0.031 |
1.0 (above ground level) |
0.035 |
resultant magnetic field |
44 |
0.030 |
|
1.5
(above ground level) |
0.034 |
resultant
magnetic field |
51 |
0.035 |
|
- |
0.035 |
three-point
average exposure
level |
|
|
Maximum magnetic
field values at the point
of interest (Apartment on second floor, near Perthenonos street
/Aradippou, in close proximity to the Overhead Lines).
Maximum magnetic field values
at the area of interest (residence).
From the measurements performed it can be concluded that the:
·
Magnetic field measurements performed at the area of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.