The measurements were performed on the25 th May 2012 at 17:20 p.m during clear weather conditions. The EMF measurements were performed for the residence at Agiou Ilarionos Street, Aradippou which is located in direct proximity to the overhead power line.
The overhead power line is rated at a nominal power of 280 MVA. At the time when the measurements were performed, the load of the overhead power line was 130 MVA. The Resultant Load of all three phases was 46 % utilisation of the nominal load power.
Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organizations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.
Reference levels for Occupational exposure ICNIRP |
|||
Frequency |
Electric Field Strength, E (V/m) |
Magnetic Field Strength, H (A/m) |
Magnetic Flux Density, B (µT) |
50 Hz |
10000 |
400 |
500 |
Reference levels for General Public exposure ICNIRP |
|||
Frequency |
Electric Field Strength, E (V/m) |
Magnetic Field Strength, H (A/m) |
Magnetic Flux Density, B (µT) |
50 Hz |
5000 |
80 |
100 |
Table 1: ICNIRP Exposure limits for Occupational and General Public exposure
The highest magnetic fi eld measurement was observed across the overhead power lines,with a value 0.232T (16m away from the starting point, at 1m height) and a percent-age of 0.232% as compared to the ICNIRP General Publicstandard.Accordingly a detailed description of the maximum measured magnetic fi elds in the area under investigation is shown in the table below.
Magnetic Field Measurements |
||||||
Measurement Method/Distance |
Maximum Magnetic Field [μT] at Z Height /m - Percentage of ICNIRP General Occoupational/Public Standard /% |
|||||
0.3m |
ICNIRP % |
1m |
ICNIRP % |
1.75m |
ICNIRP % |
|
EMF measurements along the overhead power line |
||||||
24m measurement line |
0.179 |
0.179 |
0.087 |
0.087 |
0.048 |
0.048 |
EMF measuremetns across the overhead power line |
||||||
26m measurement line |
0.152 |
0.152 |
0.232 |
0.232 |
0.212 |
0.212 |
Table 2: Magnetic Field Measurements
The highest electric fi eld measurement was observed across the overhead power lines,with a value 3.70 V/m (26m away from the starting point, at 1m height) and a per-centage of 0.074% as compared to the ICNIRP General Public standard.
Electric Field Measurements |
||||||
Measurement Method/Distance
|
Maximum Electric Field [V/m] at Z Height /m - Percentage of ICNIRP General Occoupational/Public Standard /% |
|||||
0.3m |
ICNIRP % |
1m |
ICNIRP % |
1.75m |
ICNIRP % |
|
EMF measurements along the overhead power line |
||||||
24m measurement line |
-- |
-- |
1.466 |
0.029 |
2.193 |
0.044 |
EMF measurements along the overhead power line |
||||||
26m measurement line |
-- |
-- |
3.700 |
0.074 |
2.588 |
0.052 |
Table 3: Electric Field Measurements