High Voltage Overhead Power Lines - New Aradippou Cemetery

The measurements were performed on the 10th of December 2010 at 10:10 am during clear weather conditions. The EMF measurements were performed inside the plot area and in direct proximity to the overhead power line. The following figures provide pictures of the area where EMF measurements were recorded.

Overhead power line tower No. 50 Along the overhead power lines

The overhead power line is rated at a nominal power of 316.8 MVA. At the time when the measurements were performed, the load of the overhead power line was 40.3 MVA. The resultant load of all three phases was 12.72 % utilisation of the nominal load power.

Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP.

Reference levels for Occupational exposure ICNIRP

Frequency

Electric Field Strength
E (V/m)

Magnetic Field Strength
H (A/m)

Magnetic Flux Density
B (µT)

50 Hz

10000

400

500

Reference levels for General Public exposure ICNIRP

Frequency

Electric Field Strength
E (V/m)

Magnetic Field Strength
H (A/m)

Magnetic Flux Density
B (µT)

50 Hz

5000

80

100

Table 1: ICNIRP Exposure limits for Occupational and General Public exposure

The maximum electromagnetic field values obtained are represented below and compared to the ICNIRP specified limits of General Public standards. The highest magnetic field was observed below the overhead power lines, with a value 1.06 μT (10m away from the starting point) and a percentage of 1.06 % as compared to the ICNIRP General Public standard.  

Overhead Power lines: Field Measurements

Distance from Field Line Starting Point (m)

Maximum Magnetic Field (µT) at Z Height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP 
1m

ICNIRP %

1.75m
ICNIRP %
Measurements along the Overhead Power Line

50m from Start Point
(Along the Cables)

0.77

0.77% 
0.84

0.84% 

0.90
0.90%

Measurements across the Overhead Power Line

50m from Start Point
(Horizontal to the Cables)

0.87

0.87%

0.97 

0.97% 

1.06 

1.06% 

Table 2: Maximum Magentic field measurements

Accordingly, the highest electric field was observed below the overhead power lines, with a value 512.13 V/m (20m away from the starting point) and a percentage of 10.24% as compared to the ICNIRP General Public standard.

Overhead Power lines: Field Measurements

Distance from Field Line Starting Point (m)

Maximum Electric Field (V/m) at Z Height (m)
Percentage of ICNIRP General Public Standard (%)

0.3m

ICNIRP %
1m

ICNIRP %

1.75m
ICNIRP %
Measurements along the Overhead Power Line

50m from Start Point
(Along the Cables)

--

--
414.17

8.28%

420.60
8.41%

Measurements across the Overhead Power Line

50m from Start Point
(Horizontal to the Cables)

--

--

510.83

10.21%

512.13

10.24%

Table 3: Maximum Electric field measurements