Overhead Powerlines - Dykelia - Agios Nicolaos, Famagusta

Empty Lines

This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:

·         Overhead Power Lines Dykelia-Agios Nicolaos, Famagusta, Tower 14B in close proximity to the investigated House at Agiospilios, Ormidia on the 21/08/2018 from 11:20 am until 13:00 pm.

The measurements were performed according to the measurements of low-frequency magnetic and electric fields with regard to exposure of human beings (IEC 61786:1998) and measurement procedures with regard to public exposure (IEC 62110:2009). More specifically, the largest electric and magnetic field level is found under conductors at the point on the span where the conductors are closest to the ground. Therefore, the position where the field level is the maximum was found by first measuring at 1.0 m above the ground along the path parallel to the overhead line under conductors where possible at appropriate intervals (longitudinal profile), in the range of 5 Hz – 32 kHz using the EFA-300 Isotropic Field Analyser. Then, in order to discover whether anoter peak occurs, measurements were performed at 1.0 m above the ground along the path perpendicular to the overhead line, at the point of the longitudinal profile maximum (lateral profile).

In addition, three-point measurements were performed to assess the fields at the position of interest (assuming non-uniform fields). The measurements were performed at the position of interest at three heights 0.5 m, 1.0 m and 1.5 m. above the ground or floor level of the building.

The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respect to the recommended reference levels will ensure respect to the basic restrictions. The reference levels of exposure provided in 1999/519/EC are in accordance to the Cypriot Legislation.

The maximum magnetic and electric field values measured along the longitudinal and lateral profiles of the overhead power lines and at the location of interest are summarized in the following Tables.

Empty LinesEmpty LinesEmpty LinesEmpty LinesEmpty LinesEmpty Lines

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from

starting point (m)

-2 (Lateral)

1.0 (above ground level)

0.016

resultant magnetic field

50

0.016

-1 (Lateral)

1.0 (above ground level)

0.026

resultant magnetic field

50

0.026

0 (Lateral)

1.0 (above ground level)

0.016

resultant magnetic field

50

0.016

1 (Lateral)

1.0 (above ground level)

0.026

resultant magnetic field

50

0.026

2 (Lateral)

1.0 (above ground level)

0.027

resultant magnetic field

50

0.027

Starting Point

Measurement height (m)

Electric field level (V/m)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Distance from

starting point (m)

-2 (Lateral)

1.0 (above ground level)

175.605

resultant electric field

50

3.512

-1 (Lateral)

1.0 (above ground level)

210.326

resultant electric field

50

4.207

0 (Lateral)

1.0 (above ground level)

232.368

resultant electric field

50

4.647

1 (Lateral)

1.0 (above ground level)

241.772

resultant electric field

50

4.835

2 (Lateral)

1.0 (above ground level)

253.308

resultant electric field

50

5.066

Maximum magnetic and electric field values for the investigated overhead power lines.

 

 

Starting Point

Measurement height (m)

Magnetic field level (µT)

Field quantity

Frequency (Hz)

ICNIRP

General Public (%)

Measuring point

1

(Outdoor)

0.5 (above ground level)

0.020

resultant magnetic field

50

0.020

1.0 (above ground level)

0.013

resultant magnetic field

50

0.013

1.5 (above ground level)

0.023

resultant magnetic field

50

0.023

-

0.018

three-point average exposure level

50

0.018

Maximum magnetic field values at the point of interest (house at Agiospilios, Ormidia).



From the measurements performed it can be concluded that the:

·         • Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.