   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic
  field level (µT)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public
  (%)  | 
 
| 
   Distance
  from starting
  point (m)  | 
 |||||
| 
   -2
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.016  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.016  | 
 
| 
   -1
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.026  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.026  | 
 
| 
   0
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.016  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   0.016  | 
 
| 
   1
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.026  | 
  
   resultant
  magnetic field  | 
  
   50  | 
  
   0.026  | 
 
| 
   2
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   0.027  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.027  | 
 
| 
   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Electric
  field level (V/m)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public
  (%)  | 
 
| 
   Distance from starting
  point (m)  | 
 |||||
| 
   -2
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   175.605  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   3.512  | 
 
| 
   -1
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   210.326  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   4.207  | 
 
| 
   0
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   232.368  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   4.647  | 
 
| 
   1
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   241.772  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   4.835  | 
 
| 
   2
  (Lateral)  | 
  
   1.0
  (above ground level)  | 
  
   253.308  | 
  
   resultant
  electric field  | 
  
   50  | 
  
   5.066  | 
 
Maximum
magnetic and electric field values for the investigated overhead power lines.
| 
   Starting
  Point  | 
  
   Measurement
  height (m)  | 
  
   Magnetic
  field level (µT)  | 
  
   Field
  quantity  | 
  
   Frequency (Hz)  | 
  
   ICNIRP General Public
  (%)  | 
 
| 
   Measuring point  | 
 |||||
| 
   1 (Outdoor)  | 
  
   0.5
  (above ground level)  | 
  
   0.020  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.020  | 
 
| 
   1.0
  (above ground level)  | 
  
   0.013  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.013  | 
 |
| 
   1.5
  (above ground level)  | 
  
   0.023  | 
  
   resultant magnetic field  | 
  
   50  | 
  
   0.023  | 
 |
| 
   -  | 
  
   0.018  | 
  
   three-point average exposure level  | 
  
   50  | 
  
   0.018  | 
 
Maximum
magnetic field values at the point of interest (house at Agiospilios,
Ormidia).
From the measurements performed it can be concluded that the:
·        
	•	Magnetic and electric field measurements performed at the position of interest were below the recommended General Public reference levels of the National Exposure Limits provided in 1999/519/EC.